User Manual of EM730/EM730E Series Inverter
184
Output frequency
0
0
0
Motor speed
Braking current
Brake time
Time
Time
Time
Degaussing time
Output frequency
0
0
0
Motor speed
Braking current
Brake time
Time
Time
Time
Degaussing time
Fig. 7-17 DC Braking Process for Start Fig. 7-18 DC Braking Process for Stop
In the presence of heavy loads, the motor cannot be stopped completely through
normal deceleration due to inertia. You can extend the duration of DC braking for
stop or increase the current of DC braking for stop to stop the motor from rotating.
Function
code
Function code
name
Parameter description
Unit
Leave-fa
ctory
value
Attribute
F04.24
Flux braking gain 100-150 (100: no flux braking)
100
〇
When the magnetic flux braking is valid (F04.24>100), the motor can be quickly slowed
down by increasing its magnetic flux, and the electric energy can be converted into thermal
energy during motor braking.
Flux braking may lead to quick deceleration, but the output current may be high. The flux
braking intensity (F04.24) can be set restriction and protection to avoid damage to the motor. If
flux braking is not applied, the deceleration time will be extended but the output current will be
low.
Function
code
Function code
name
Parameter description
Unit
Default
setting
Attribute
F04.26
Start mode after
protection/free stop
0: start according to F04.00
setting mode
1: start of speed tracking
0
〇
The start after the protection or free stop may be enabled by default according to the F04.00