9
A
B
A.
Cable compartment lid
B.
"ON" LED light
1.OVERVIEW
2.Connections/buttons/led lights
USB CONNECTION
CONNECTION AT SIN.EQRTU1T
Before connecting anything, switch the power off, complete the cabling, close the lid and
power the device on.
TROUBLESHOOTING
1) The device does not start:
2) The blue LED light does not stop flashing:
3) Not all the meters are revealed:
3.WALL FASTENING AND CABLE PASS
Temperature range:
Ingress Protection:
Protection Class:
Fastening:
Dimensions:
Power supply:
Consumption:
Radio Frequency:
W. M-Bus Mode:
Max distance between
two RPT:
7.TECHNICAL DATA
1
2
3
+55°C
SIN.EQRPT868XT -QuickStartGuide
-20°C
DOCUMENTATION DOWNLOAD
: http://www.sinapsitech.it/en/area-download/
SIN.EQRPT868XT_QSG_2.4_en
Wireless M-Bus 868 MHz Sinapsitech
℗
REPEATER
Sinapsi
Srl r
eserv
es the ri
ght to mak
e changes to
this pro
duct witho
ut an
y notice
- in case of network power supply, check that the power is on
- in case you are using a USB port, check the USB cable quality and that the PC is enabled to handle
500 mA of electrical power
- check that the meters that were not revealed are not too distant from SIN.EQRPT868XT or that
the signal is not disturbed by thick concrete or metal walls
- check that the devices are on the list loaded in SIN.EQRPT868XT or that the W. M-Bus devices
list receivable from SIN.EQRPT868XT is not blocked
- warning: some W. M-Bus devices transmit periodically (within hours)
- check that the MESH network is not interrupted using SIN.EQRTU1T web interface or SIN.EQSW1 sw
- Receiver and radio repeater for W. M-Bus devices (EN13757-4)
- Remarkable radio coverage due to multi-hop network
architecture (MESH)
- Manages up to 500 meters
- Last acquired data stored in a non-volatile memory
- Easy installation with software setup
- Simple and elegant design
- 100..240Vac power or via USB
- "Wall mounting" like installation
- USB interface for local data reading
- Optional WEB interface usable with SIN.EQRTU1T
1
2
1 - Power input 100..240Vac (with clips)
2 - Multifunction button
3 - Multifunction button
4 - Reset button
5 - USB port
3 4
6 - MESH network TX-RX LED
7 - W. M-Bus network TX-RX LED
8 - Signal/reception level LED
9 - State LED
5
6 7
8
SIN.EQRPT868XT repeater devices are provided with a MESH- ID=1 and channel 13.
Make sure that all the repeaters and/or SIN.EQRTU1T have the same MESH network ID and radio
channel through SIN.EQSW1
Operative: -20°C ... +55°C
Storage: -25°C ... +85°C
IP 40 (EN60529)
II
wall clipped
LxHxP 160x160x35mm
100..240Vac 50/60Hz
USB (5Vdc, 500mA) for commissioning
4.5W
868MHz - Max transmission power: 27dBm
S / T / C +T / S & C+T
500mt free field - 40mt in building
- check that the device SIN.EQRTU1T is on and that the antenna is connected and in good position
(avoid placing it in switchboards or shielded environments)
- 1 blink "RAM memory error", 2 blinks "W.M-Bus radio module error",
3 blinks "MESH radio module error", 4 blinks "FLASH memory error", 5 blinks "Real Time Clock error"
- If turning off and restarting the SIN.EQRPT868XT, the error does not reset, the hardware
must be replaced.
- check that SIN.EQRPT868XT is at least 5 metres distant from SIN.EQRTU1T and from other
SIN.EQRPT868XT
- check that the ID and the MESH network channel are correct using SIN.EQSW1 sw and are the
same ones used by SIN.EQRTU1T
1 - upper hole
2 - low pre-hole
3 - cable pass pre-hole
4 - power supply connection
6. REPEATER NETWORK CONFIGURATION
1. Power on SIN.EQRTU1T, connect to web interface and start antenna and device scan following
the user’s manual
2. Power on the first device SIN.EQRPT868XT to be installed and move it away to a minimum distance
of 5 metres from SIN.EQRTU1T
3. Fixed blue SIN.EQRPT868XT LED shows the connection to the MESH network
4. Once connected, it shows the MESH radio signal quality to the gateway, by turning on the green
front LED, 1 – insufficient reception, 2 – sufficient, 3- good, 4 – excellent
5. Put SIN.EQRPT868XT in a place where the reception signal is >=2 and the reception of all the W. M-Bus
devices you expect to receive with this antenna is satisfactory
6. Check through SIN.EQRTU1T web interface or through SIN.EQSW1 software and a PC connected to the
antenna by USB that W. M-Bus devices, that you want to receive, reach the SIN.EQRPT868XT
7. Fasten the SIN.EQRPT868XT and proceed with powering a second repeater keeping it at least 5 metres
away from both the SIN.EQRPT868XT and SIN.EQRTU1T
8. Once connected, it shows the MESH radio signal quality to the gateway, by turning on the front LED,
so proceed as for the first SIN.EQRPT868XT.
a) The scanning phase is 12 hours. You can modify its duration through SIN.EQRTU1T
b) You can have various independent SIN.EQRPT868XT networks in the same building. In that case,
you need to have different ID or channel for each SIN.EQRPT868XT group and the relative
SIN.EQRTU1T.
You can modify these parameters through SIN.EQSW1 software installed on a pc and connected via
USB to SIN.EQRPT868XT, see user’s manual for details.
c) In case the receiver receives more than 500 W. M-Bus devices or it receives devices belonging
to other plants, it might be necessary to make it selective. Therefore, you can load a list of W. M-Bus
devices marked by their serial number through SIN.EQSW1 software.
In this way, the repeater will receive the data exclusively from the listed devices.
d) The USB / Mini USB cable is not included and is not present in the package.
2 x Anchor 5x25
2 x Screws 5x30
2 x Glands
1 x SIN.EQRPT868XT
4.PACKAGE CONTENT
N
Power
supply
connection
2 x Screw 2,2x9,5
1 x clamp headband
SIN.EQRTU1T
MIN 5 m
MIN 5 m
MIN 5 m
USB
Mini USB
5.POSITIONING AND OPERATING DISTANCES
MAX 25 m
MAX 25 m
SIN.EQRTU1T
SIN.EQRPT868XT
FLOOR 1
FLOOR 0
MAX 15 m
SIN.EQRPT868XT
FASTENING
WALL
W
ALL
CEILING
MIN
20 cm
MIN
20 cm
1) Fix the SIN.EQRPT868XT repeater on fastening wall at a minimum
distance of 20 cm from the ceiling and from the adjacent wall.
2) The maximum operating distance between the devices
installed on the same floor is 25 meters, with no major
obstacles such as reinforced concrete or metal walls, columns
or beams or other metal structures.
3) The maximum operating distance between the devices
installed on different floors is 15 meters.
MIN 5 m
SIN.EQRPT868XT
MIN 5 m
SIN.EQRPT868XT
MAX 25 m
MAX 15 m
Manufactured by SINAPSI SRL - Via delle Querce 11/13 - 06083 Bastia Umbra (PG) - Italy
For details on the configuration of the SIN.EQRPT868XT using the buttons, see the back of this
document, in the dedicated section.
L
max 2x1,5 mm
2
o 6 mm
4