background image

CONNECTING EXTERNAL EQUIPMENT 

20221933 / E

 

25

 

2.4

 

Digital Output ports (TB11) 

Signal description 

 

PIN NO. 

SIGNAL NAME 

COMMENTS 

Out + 

Digital Output 1 

System Failure 

Signal high: Standard mode 

Signal low: System failure (ECDIS 

shut down) 

Out - 

Out + 

Digital Output 2 

Alarm sound control 

Signal low: No audible alarm/or alarm 

muted 

Signal high: Audible alarm present 

Out - 

Out + 

Digital Output 3 

Alarm present on ECDIS  

Signal low: No alarm present 

Signal high: Alarm present 

Acknowledge of alarms does not 

change the signal. 

Out - 

Strap settings for inverting signals 

The digital output is 24V, determined by the strap settings on S1 
– S3 as shown in the table below: 

 

 

DIGITAL 

OUTPUT 1 

DIGITAL 

OUTPUT 2 

DIGITAL 

OUTPUT 3 

Normally open 

 

 

 

Normally closed 

(Factory default) 

 

 

 

LED Indication 

D16, D18 and D56 are used to indicate active relay on digital 
output ports as indicated in the table below. 

 

 

 

 

LED 

LED STATUS 

COMMENT 

D16 (Output 1) 

ON 

Relay active 

D18 (Output 2) 

D56 (Output 3) 

 

 

 

Summary of Contents for Simrad CS68

Page 1: ...www simrad yachting com A brand by Navico Leader in Marine Electronics Installation Manual Simrad CS68 ECDIS English ...

Page 2: ...9CE MO19BE E 160909 NG JGV THE New software release 3 1 adapted to new 19 ECDIS monitors and new MC50 MKII Minor update to illustrations 2005 2009 Simrad AS All rights reserved No part of this work covered by the copyright here on may be reproduced or otherwise copied without prior permission from Simrad AS The information contained in this document is subject to change without prior notice Simrad...

Page 3: ...s connected to a CS68 system 3 Software configuration How to configure the CS68 software 4 Installation approval Check lists that should be used to verify correct installation of a CS68 system 5 Technical specifications Hardware specification for all units included in a CS68 system 6 Spare parts listing List of all standard and optional units included in the CS68 system 7 Drawings Drawings diagram...

Page 4: ...INSTALLATION MANUAL iv 20221933 E THIS PAGE INTENTIONALLY LEFT BLANK ...

Page 5: ... Connecting the monitor s 16 1 13 Connecting the system to Internet 18 1 14 Connecting optional equipment 19 2 CONNECTING EXTERNAL EQUIPMENT 21 2 1 General 22 2 2 Serial I O ports TB1 TB8 23 2 3 Digital Input ports TB10 24 2 4 Digital Output ports TB11 25 2 5 Grounding external cables 26 2 6 Connection of Radar processor unit 27 3 SOFTWARE CONFIGURATION 28 3 1 The System configuration dialog 29 3 ...

Page 6: ...60 6 SPARE PART LISTING 61 6 1 Main components 62 6 2 Accessories 63 7 DRAWINGS 65 7 1 Drawings overview 66 7 2 MC50 Marine Computer 67 7 3 Cherry keyboard 70 7 4 Loudspeaker 71 7 5 FB200 Filter box 72 7 6 Chart Interface unit 73 7 7 Alarm Reset unit External ON OFF switch 74 7 8 COP10 Option 75 7 9 COP20 COP30 OPTION 76 7 10 CS68 ECDIS Cabling diagram 77 7 11 Computer interface board Component la...

Page 7: ...INSTALLATION 20221933 E 1 1 INSTALLATION This section holds descriptions for unpacking and handling the equipment and for mechanical and electrical installation of all units in the CS68 system ...

Page 8: ...CS68 ECDIS 2 20221933 E 1 1 General A CS68 system may be used as a main chart system or as a back up in an ECDIS system ...

Page 9: ...rface unit Cherry keyboard Logitech TrackMan wheel Splitter cable for TrackMan wheel and keyboard Loudspeaker Alarm Reset unit The basic system may be expanded with a second monitor a COP20 30 Operator panel a COP10 remote operator panel a Radar Processor unit and with a printer If no COP20 30 is included in the system an optional switch may be installed to turn the system ON OFF OPTIONAL EQUIPMEN...

Page 10: ...Unpacking and handling Care should be taken when unpacking and handling the equipment A visual inspection should be made to see that the equipment has not been damaged during shipment and that all components and parts are present ...

Page 11: ...rature range and cable length The CS68 units are designed to operate within the temperature range of 0 C to 55 C However it is recommended that adequate ventilation air conditioning is provided in order to keep the ambient operating temperature at 20 C It is also recommended that the area around the units is kept relatively free from dust and build up static electricity ...

Page 12: ...quipment should not be stored upon the MC50 unit The unit should be mounted as close as possible to the FB200 Filter box as the cable length between FB200 and MC50 is limited to 0 45 m The mounting location should allow access to the power button the DVD and the floppy drive It is also necessary to have working area when replacing the air inlet fans dust filter Refer dimensional drawing showing re...

Page 13: ...er cabinet to the mounting plate Monitor One or two Hatteland Display series 1 Redesign 19 20 1 23 and 27 monitor must be part of the ECDIS system The monitors must have equal size A separate Instruction manual is delivered with the monitor This manual includes installation procedures as well as dimensional drawings The monitor must be validated to matrox P690 display adapter to be ECDIS approved ...

Page 14: ...n different chart systems and it is therefore delivered with different text stickers to match the system Note If the Alarm Reset unit is used in an ECDIS system the ECDIS sticker should be used If used in an ECDIS back up system the CS68 sticker is to be used Use the following procedure when mounting the Alarm reset unit 1 Fix the ECDIS or the CS68 sticker to the button Refer Note above 2 Attach t...

Page 15: ...onal drawing on page 76 and the cut out template on page 85 2 Lift the four removable corners from the panel 3 Locate COP20 30 in the hole and secure the unit to the panel with four 4mm screws 4 Reposition the removable corners on the panel COP10 Remote Operator panel Option COP10 is designed to be mounted in the helmsman chair s armrest 1 Cut the necessary holes in the armrest where COP10 is to b...

Page 16: ...ding the units The computer Chart interface unit and FB200 should have a proper ground connection from the units ground terminal The wires should be as short as possible and have a cross section of at least 16mm2 gauge GROUND TERMINALS ...

Page 17: ...21933 E 11 1 7 MC50 MKII computer s terminal layout The illustration below shows the MC50 unit s back side The terminal layout on your MC50 unit may differ from the illustration and more less terminals may be available ...

Page 18: ...nals as shown on the figure below Note This cable is not supplied with the equipment It should have a cross section of at least 2 5mm2 gauge 2 Connect the cable from FB200 to the 24V DC power in jack on the MC50 computer 3 Secure the cable to the fixing bracket to avoid that vibration should cause the plug to loose connection Alarm supply 24V alarm supply from the vessel s alarm supply has to be c...

Page 19: ...face unit cable connections Connections between the MC50 computer and the Chart Interface unit are made by three cables The cables are pre made from factory For cables lengths refer Cabling section page 49 Refer also to CS68 Cabling diagram page 77 ...

Page 20: ...se and speaker Cherry keyboard and TrackMan Wheel are connected to the MC50 computer The speaker is connected to the Chart Interface unit Note Cherry keyboard and TrackMan Wheel has to be connected via the splitter cable Refer CS68 Cabling diagram page 77 ...

Page 21: ...INSTALLATION 20221933 E 15 1 11 Using the USB connection If any equipment is connected to the USB port the cable must be equipped with one of the supplied ferrite beds KG USB 4 ...

Page 22: ...I A 9 pin serial cable must be connected between COM 9 or COM 10 on MC50 MKII and the monitor s 2 m 24V DC SUPPLY COM9 MONITOR 2 COM10 2 m J4 DVI VGA 1 9 m 24V DC SUPPLY MC50 MKII PART OF 1 9 m DVI VGA COMPUTER MONITOR 1 If longer cable lengths are required a high quality VGA cable must be used together with the supplied DVI VGA converters Note Do not use the VGA output on J1 on the rear of MC50 M...

Page 23: ...mrad s support site http www simrad yachting com en Support The support site is authorized for OEM dealers and distributors A password is required to get access to this web site The selected COM port s need to be defined in the System Configuration dialog to make sure that automatically backlight adjustment are done according to ECDIS regulations Refer Output configuration page 37 ...

Page 24: ...hart update The system is connected by using a shielded Ethernet cable NOTE Pin 1 and 3 or pin 2 and 6 must be broken To fulfill the ECDIS requirements the system must be connected via a switch that electrically separates the ECDIS from the Internet The Ethernet cable must be equipped with one of the supplied ferrite beds SFC 10 ...

Page 25: ... unit is connected between the keyboard or the keyboard plug on COP20 30 and the splitter cable as shown on the figure below If no COP20 30 is installed an optional ON OFF switch may be connected to TB15 in the Chart Interface unit OPTION COP20 30 5 m KEYBOARD MOUSE OPTION ON OFF SWITCH 5 m 2 ALARM RTN GREEN 6 GREY YELLOW PINK 4 5 3 5 12V GND 6 ON ON 4 3 BROWN WHITE 1 2 YELLOW GREEN 6 5 TB15 ALARM...

Page 26: ...CS68 ECDIS 20 20221933 E THIS PAGE INTENTIONALLY LEFT BLANK ...

Page 27: ...CONNECTING EXTERNAL EQUIPMENT 20221933 E 21 2 CONNECTING EXTERNAL EQUIPMENT This section described how external equipment is connected to the CS68 system ...

Page 28: ...e Computer Interface board in the Chart Interface unit Component layout showing terminals strap location and diodes on this board is shown on page 78 Connect the signal cabling from the external equipment as per the manufacturer s specification and according to the description in the following pages ...

Page 29: ...s for each of the eight I O channels are indicating signals passing the channels by steady interrupting or flashing lights as shown in the table below LED LED STATUS COMMENTS Tx Interrupting Transmitting data Steady No data transmitted Tx Flashing Transmitting data Off No data transmitted Rx Interrupting Receiving data Steady No data received Rx Flashing Receiving data Off No data received ...

Page 30: ...orts TB10 Signal description PIN NO SIGNAL NAME COMMENTS 1 In Digital input 1 Shortcut 0 5 sec to silence all alarms 2 In 3 In Digital input 2 Spare 4 In 5 In Digital input 3 Spare 6 In LED indication There are no LEDs for the Digital Input ports ...

Page 31: ...al Output 3 Alarm present on ECDIS Signal low No alarm present Signal high Alarm present Acknowledge of alarms does not change the signal 6 Out Strap settings for inverting signals The digital output is 24V determined by the strap settings on S1 S3 as shown in the table below DIGITAL OUTPUT 1 DIGITAL OUTPUT 2 DIGITAL OUTPUT 3 Normally open Normally closed Factory default LED Indication D16 D18 and...

Page 32: ...ld be properly terminated to the Chart Interface unit s grounding bar as follows 1 Strip the cable s insulation and pull the screen backward to cover the insulation 2 Fix the cable screen to the grounding bar by a wire strap Tighten well to make sure the screen has good contact ...

Page 33: ...dar Processor unit is connected by the USB cable to a spare USB connector on the MC50 Mk2 For connection to the vessel radar system refer to separate manual If the radar video is not referenced to CCRP the offset should be set in the Radar position offset field in the Radar menu Tools Radar ...

Page 34: ...CS68 ECDIS 28 20221933 E 3 SOFTWARE CONFIGURATION This section describes how to configure the CS68 software ...

Page 35: ...have to be performed before the CS system is ready for operation To avoid unintended alteration of system parameters the System Configuration dialog is password protected Use the following procedure to open the System Configuration dialog 1 Press the Setup menu followed by the System Configuration command A dialog will request a password before it is possible to enter the system configuration 2 Ty...

Page 36: ...are applied and the dialog box remains displayed The different tabs in the System Configuration dialog are described in the following pages Ref page Inputs Used to configure external devices 32 Outputs Used for configuring the output format 37 Checksum Used for checksum test for received data 38 Aux settings Used for different hardware and software settings 39 Misc Used for different operator para...

Page 37: ...m Configuration dialog is used for configuring the input format for each interfacing serial channel The tab is also used to delete or edit an already defined input All defined input devices are listed alphabetically in the Input tab If no input device is configured the dialog will be empty ...

Page 38: ... Device Type Drop down field with available device types Data Format NMEA format and Baud Rate for the device Available alternatives are dependant on selected device type Baud Rate NMEA Header NMEA header for the device This header must be specified if multiple talkers with identical telegram type e g GLL are connected Listen for Selectable sentences for the device Available sentences may be displ...

Page 39: ...ntenna position must be entered into the system to give the correct ship position If two equal navigators GPS with antennas are installed as indicated on the figure below and if correct antenna offset is entered there should be no position difference between them The ship will obtain the same position in the chart even if the sensors are exchanged If an ARPA MARPA is connected to the CS system in ...

Page 40: ...PA log gyro position reference sentences and Ethernet connection All tabs in this dialog have text specifying the different data fields as shown in the arp tab shown below Modifying an input device A device can be modified by pressing the Edit button or by double clicking the specific device in the Inputs tab in the System Configuration dialog The Input Config dialog will be displayed and paramete...

Page 41: ... Deleting an input device A defined input device is deleted by activating the device in the Inputs tab and then pressing the Delete button To avoid unintended removal of a device the selection has to be confirmed by pressing the OK button ...

Page 42: ...o the Inputs tab in the System Configuration dialog Freeze Stops the text from scrolling Clear Clears the text field in the dialog Hex ASCII Toggles the log data between hexadecimal and ASCII characters Log Activate Saves the monitored log data to a file A new dialog for selecting file name and location will be displayed When logging is activated the button will change to Log Deactivate Pressing t...

Page 43: ...ecified Minimum baudrate Value increasing as output messages are selected Note that this value not should exceed the value set for the input baudrate on the same com line Clear Clear all selected output message sentences Output messages Available sentences for the output device The output is NMEA0183 Standard sentences and at least one of these sentences must be enabled Output line for controlling...

Page 44: ... sum with the checksum transmitted by the device When the calculated and the received checksum not are identical the settings in the Checksum tab in the System Configuration dialog will decide whether the CS system will use or reject these data Each serial line has its own checksum configuration Max Sequential Checksum Errors Number of sequential checksum errors detected before a checksum alarm wi...

Page 45: ...xample below 4 decimals are selected NMEA decimals Number of decimals used in the data output sentences Stepper Gyro Not used Voice Alarm Toggles voice alarm function ON OFF Start Route Replication Enables route replication between ECDIS and Backup machine in PLECDIS configurations Routes created on one system will then automatically be copied to the other system ...

Page 46: ...to local time Screen size Used for setting correct diagonal screen size When pressing the Start RULER button a new dialog for entering screen size is opened Press the Measure the Screen button to open a new dialog used for measuring a selected area directly on the monitor Measure width and height of the white area and enter the values in inches of mm ...

Page 47: ... be restarted to synchronize the screen settings Alarm Test By pressing this button the built in alarm system will issue an alarm for 5 seconds Backup Manager Used for starting the backup manager Refer the separate CS68 Operator Manual Clean all registry settings Cleans all registry settings when the system is shut down This will force the system to use default values for all system variables Caut...

Page 48: ...ze Used when the actual ship is larges that the minimum ship symbol Note that the reference offset points are calculated from the vessel s center point Turn Radius Used as default value when a route is created Crab Factor Used for autopilot turn start calibration Wheel over time Response time in seconds from a rudder command is given until the vessel starts turning This parameter is dependant on v...

Page 49: ...INSTALLATION APPROVAL 20221933 E 43 4 INSTALLATION APPROVAL This section includes check lists that should be used to verify correct installation of the CS68 system ...

Page 50: ... E 4 1 General When all units are installed external equipment connected and the software configured according to the previous sections the installation should be verified according to the check lists in the following pages ...

Page 51: ...ed MC50 computer 6 Monitor 1 7 Monitor 2 7 FB200 Filterbox 7 Chart Interface unit 8 Loudspeaker 8 Alarm Reset unit 8 Optional operator panels 9 Optional External ON OFF switch 9 Units properly grounded 10 Power connection Procedure Ref page Y N NA Comment Power connected to MC50 12 Alarm supply connected to TB9 in Chart Interface unit 12 ...

Page 52: ... to TB14 on Chart Interface unit TB1 on MC50 to TB16 on Chart Interface unit J3 on MC50 to J1 on Chart Interface unit Optional external ON OFF switch connected to TB15 in Chart Interface unit Optional operator panels connected to MC50 and Chart Interface unit 18 External equipment Procedure Ref page Y N NA Baud Rate Type of equipment Sentence External equipment connected to input output ports in C...

Page 53: ... Minimum reference systems configured GPS 32 GPS datum 33 GPS Antenna offset 33 Gyro 32 Log 32 Display units selected 41 Screen size set correctly 40 Ship information and parameters entered 42 General check Procedure Ref page Y N NA Comment Alarms operational 41 Time updated correctly from GPS 40 Keyboard and mouse operative System back up Procedure Ref page Y N NA Comment Back up made to Library ...

Page 54: ...CS68 ECDIS 48 20221933 E 5 TECHNICAL SPECIFICATIONS This section lists hardware specification for all units included in the CS68 system ...

Page 55: ...ONS 20221933 E 49 5 1 Cabling Cable length for standard and optional units in the CS68 system is shown on the figure below and in the table on next page 20 OPTIONAL EQUIPMENT 1 8 9 7 19 3 2 4 14 13 15 6 5 12 16 17 18 10 11 ...

Page 56: ...er 7 1 25 m J3 MC50 J1 Chart Interface unit 8 1 25 m TB1 MC50 TB16 Chart Interface unit 9 1 3 m Audio 10 Supplied with monitor may be delivered by others 11 12 5 m Part of external ON OFF switch 13 5 0 m System Part of COP20 COP30 14 1 5 m Keyboard 15 1 7 m Mouse 16 5 m Part of COP10 17 Supplied with monitor may be delivered by others 18 19 Ordered from printer supplier 20 TBA Part of Radar Proces...

Page 57: ... 5 2 MC50 computer unit Height 196 mm Width 363 mm Depth 428 mm Net weight 9 5 Kg Color Black Environmental Protection IP22 Temperature range Operating 0 to 55 C 32 to 131 F Storage 15 to 70 C 5 to 158 F Dimensional drawing page 67 onwards ...

Page 58: ...CS68 ECDIS 52 20221933 E 5 3 Loudspeaker Height 110 mm Width 110 mm Depth 48 mm Color Black Effect PMPO 80 watt max Frequency range 20Hz 80 kHz Environmental Protection IP22 Dimensional drawing page 71 ...

Page 59: ...ilterbox Height 50 mm Width 177 mm Depth 103 mm Net weight 0 5 Kg Power 24V DC Power consumption 140W Color Black Environmental Protection IP32 Temperature range Operating 0 to 55 C 32 to 131 F Storage 15 to 70 C 5 to 158 F Dimensional drawing page 72 ...

Page 60: ...unit Height 280 mm Width 312 mm Depth 60 mm Net weight 2 3 Kg Power 24V DC Power consumption 50W Color Black Environmental Protection IP22 Temperature range Operating 0 to 55 C 32 to 131 F Storage 15 to 70 C 5 to 158 F Dimensional drawing page 73 ...

Page 61: ...CATIONS 20221933 E 55 5 6 Cherry keyboard Height 130 mm Width 280 mm Depth 37 mm Net weight 0 5 Kg Color Black Temperature range Operating 0 to 55 C 32 to 131 F Storage 15 to 70 C 5 to 158 F Dimensional drawing page 70 ...

Page 62: ...CS68 ECDIS 56 20221933 E 5 7 TrackMan wheel Height 145 mm Width 90 mm Depth 58 mm Net weight 0 2 Kg ...

Page 63: ...TECHNICAL SPECIFICATIONS 20221933 E 57 5 8 Alarm Reset unit Height 72 mm Width 72 mm Depth including cable bend 70 mm Net weight 0 35 Kg Dimensional drawing page 74 ...

Page 64: ...l Option Height 220 mm Width 440 mm Depth 135 mm incl cable bend Net weight 3 8 Kg Color Black Illumination Adjustable Environmental Protection IP56 Temperature range Operating 0 to 55 C 32 to 131 F Storage 15 to 70 C 5 to 158 F Dimensional drawing page 76 ...

Page 65: ...n Height 144 mm Width 72 mm Depth 76 mm incl securing screw Net weight 0 65 Kg Color Black Enclosure material Aluminum Mounting Panel mounted Environmental Protection IP32 Temperature range Operation 0 to 55 C 32 to 131 F Storage 15 to 70 C 5 to 158 F Dimensional drawing page 75 ...

Page 66: ...CS68 ECDIS 60 20221933 E 5 11 External ON OFF switch Option Height 72 mm Width 72 mm Depth including cable bend 70 mm Net weight 0 35 Kg Dimensional drawing page 74 ...

Page 67: ...SPARE PARTS LISTING 20221933 E 61 6 SPARE PART LISTING This section includes part numbers for all standard and optional units that may be included in a CS68 system ...

Page 68: ...0 Hz TBA JH23T12 MMD 1600 1200 60 Hz TBA JH27T11 MMD 1920 1200 60 Hz 26055046 FB200 Filterbox 26056200 Chart Interface unit 44176022 Cherry keyboard 44169712 TrackMan wheel 26056218 Loudspeaker 26056473 Alarm reset unit 26053231 COP10 Remote operator panel 26053355 COP20 Operator panel 26053207 COP30 Operator panel 26056713 External ON OFF switch TBA Radar Processor unit ...

Page 69: ...SPARE PARTS LISTING 20221933 E 63 6 2 Accessories PART NUMBER DESCRIPTION 44142131 Air inlet filter ...

Page 70: ...CS68 ECDIS 64 20221933 E ...

Page 71: ...DRAWINGS 20221933 E 65 7 DRAWINGS This section includes drawings diagrams and cut out templates for units in the CS68 system ...

Page 72: ...617 A Alarm Reset unit External ON OFF switch Dimensional drawing D4 605650 A FB200 dimensional drawing D3 604913 A COP10 OPTION Dimensional drawing N3 605303 A COP20 COP30 OPTION Dimensional drawing N1 605304 A CS68 Chart system Cabling diagram N3 605644 C Computer interface board component layout N4 605514 D Loudspeaker Panel cut out N4 605619 A Alarm Reset unit External ON OFF switch Panel cut ...

Page 73: ...DRAWINGS 20221933 E 67 7 2 MC50 Marine Computer Front view ...

Page 74: ...CS68 ECDIS 68 20221933 E Side view ...

Page 75: ...DRAWINGS 20221933 E 69 Bottom view ...

Page 76: ...CS68 ECDIS 70 20221933 E 7 3 Cherry keyboard ...

Page 77: ...DRAWINGS 20221933 E 71 7 4 Loudspeaker ...

Page 78: ...CS68 ECDIS 72 20221933 E 7 5 FB200 Filter box ...

Page 79: ...DRAWINGS 20221933 E 73 7 6 Chart Interface unit ...

Page 80: ...CS68 ECDIS 74 20221933 E 7 7 Alarm Reset unit External ON OFF switch ...

Page 81: ...DRAWINGS 20221933 E 75 7 8 COP10 Option ...

Page 82: ...CS68 ECDIS 76 20221933 E 7 9 COP20 COP30 OPTION ...

Page 83: ... 3 PINK GREY 5 4 BROWN WHITE 2 1 RED BLACK BLACK RED 2 5 6 3 4 1 3 RED BLUE 4 YELLOW GREEN 2 1 GND ALARM RTN ON 12V TX GND TX RX RX 4 5 1 2 3 TB1 TX 4 GND 5 RX TX RX 1 2 3 TB2 TX 4 GND 5 RX TX RX 1 2 3 TB3 TX 4 GND 5 RX TX RX 1 2 3 TB4 TX 4 GND 5 RX TX RX 1 2 3 TB5 TX 4 GND 5 RX TX RX 1 2 3 TB6 TB7 GND TX RX RX TX 5 4 2 1 3 TX RX RX TX GND 3 4 5 1 2 TB8 J1 AUDIO IN SERIAL LINE NO 1 NO 2 LINE SERIA...

Page 84: ...CS68 ECDIS 78 20221933 E 7 11 Computer interface board Component layout ...

Page 85: ...DRAWINGS 20221933 E 79 7 12 Loudspeaker Panel cut out ...

Page 86: ...CS68 ECDIS 80 20221933 E ...

Page 87: ...DRAWINGS 20221933 E 81 7 13 Alarm Reset unit External ON OFF switch Panel cut out ...

Page 88: ...CS68 ECDIS 82 20221933 E ...

Page 89: ...DRAWINGS 20221933 E 83 7 14 COP10 Panel cut out 70mm 142mm ...

Page 90: ...CS68 ECDIS 84 20221933 E ...

Page 91: ...DRAWINGS 20221933 E 85 7 15 COP20 COP30 Panel cut out 435mm 215mm ...

Page 92: ...Simrad CS68 ECDIS Installation Manual English Doc no 20221933 Rev E 20221933E ...

Reviews: