1.0 – IMPORTANT SAFETY INFORMATION  

 

CAUTION:   DO NOT VOID YOUR WARRANTY- FOLLOW THESE INSTRUCTIONS 
CAREFULLY AND REVIEW WARRANTY DOCUMENT PRIOR TO INSTALLATION 

1.1 - Safety Instructions 

1.

 

Before assembling or using the SimpliPhi Battery Only Storage System for Six Batteries (BOSS.6), read 
all instructions and cautionary markings included in this manual. 

2.

 

Perform all electrical work on the BOSS.6 Enclosure in accordance with local, state and federal 
electrical codes. 

3.

 

The BOSS.6 Enclosure is NEMA 3R-rated for a degree of protection against debris, as well as rain, 
sleet and ice. The Enclosure is NOT watertight and should therefore be protected against excessive 
exposure to liquids. 

4.

 

To reduce the chance of short-circuits and/or electrical shock, always use insulated tools when 
installing or working with this equipment. For the same reason, remove all jewelry such as rings, 
watches, bracelets, etc., and wear insulated rubber electrical gloves when installing or performing 
maintenance on the BOSS.6 Enclosure or the PHI battery modules contained within. 

5.

 

Before assembling or using the BOSS.6, inspect the shipment and the product itself for signs of 
damage. Do not use the BOSS.6 Enclosure if there are indications that it has been damaged during 
shipping or otherwise. Refer to Section 3.1 – Inspection of this Guide for further instruction. 

6.

 

Do not dismantle the BOSS.6 Enclosure; there are no user-serviceable parts contained in this product. 
Doing so will Void the Warranty. 

7.

 

The BOSS.6 Enclosure is designed for the housing and wiring of up to 6 SimpliPhi PHI 3.8, 3.5, or 3.4 
kWh batteries (measuring ~13.5” wide x 15.5” high with terminals x 8.1” deep) or up to 6 SimpliPhi PHI 
2.9, 2.7 or 2.6 kWh batteries (measuring 11.25” W x 12.75” high with terminals x 9.5” deep). Check 
with SimpliPhi Technical Support (

[email protected]

) prior to using the BOSS.6 

Enclosure with any other PHI battery models. 

8.

 

Prior to installing or performing maintenance on the BOSS.6 Enclosure, turn all included PHI Battery 
module built-in circuit breakers’ “ON/OFF” switches to the “OFF” position, and disconnect all wiring 

Summary of Contents for BOSS.6

Page 1: ...SIMPLIPHI POWER INC REV020620...

Page 2: ...Table of Contents 1 0 IMPORTANT SAFETY INFORMATION 1 1 1 Safety Instructions 1 1 2 Limitations of Use 2 2 0 Product Description 2 2 1 Introduction 2 2 2 Overview 2 2 3 Specifications 3 3 0 Installati...

Page 3: ...celets etc and wear insulated rubber electrical gloves when installing or performing maintenance on the BOSS 6 Enclosure or the PHI battery modules contained within 5 Before assembling or using the BO...

Page 4: ...es Warranty 10 Verify polarity at all battery module connections with a standard voltmeter before 1 energizing the system and 2 turning the PHI Battery s circuit breaker ON OFF switch to the ON positi...

Page 5: ...the PHI Batteries already included in the fully integrated AccESS or ExprESS units All PHI batteries must be fully charged BEFORE commissioning Failure to do so will Void the Warranty As outlined in t...

Page 6: ...ge on the receiving document before signing for receipt of the equipment Damage claims should be filed directly with the carrier Not doing so can limit your ability to claim damage of equipment with t...

Page 7: ...S 6 Carbon Steel Enclosure 1 2 Shelf Mounted Within the Enclosure 1 3 Built in Enclosure Vent 2 7 Built in Corrosion Resistant Equipment Cooling Fan 1 8 20 Long High Strength Steel Hex Head Screw 2 9...

Page 8: ...wo or three PHI batteries SKU numbers BB 2 and BB 3 respectively are sold separately and may be purchased from any SimpliPhi distributor https simpliphipower com distributors o The built in 5 point te...

Page 9: ...ltraflex Blue cables with 3 8 lugs 3 Use pairs of battery cables to wire from each PHI battery to the terminal blocks 6 total 8 AWG Arctic Ultraflex Blue cables with 3 8 lugs may be special ordered di...

Page 10: ...s The BOSS 6 Enclosure can be installed directly adjacent to the AccESS or BOSS 6 fully integrated units Ensure that any ventilation is not blocked on the sides of the AccESS or BOSS 6 units If mounti...

Page 11: ...s masonry bolts or carriage bolts minimum diameter 3 3 Assembling the BOSS 6 Enclosure 4 Make sure all PHI battery module circuit breakers are in the OFF position Prepare the battery modules for insta...

Page 12: ...flat washers included with cabinet 3 8 lock washers and 11 16 stainless steel hex nuts originally included on the batteries Tighten the nuts to 160 in lbs 9 Attach positive interconnecting busbars di...

Page 13: ...ar to terminals on a SimpliPhi battery video Figure 3 Interconnecting Busbars Attach to PHI Battery Terminals Interconnecting busbars are not included with Enclosure 10 Wire the negative interconnecti...

Page 14: ...sbars are ordered from SimpliPhi or from a SimpliPhi distributor they will come with the 3 8 flat washers 3 8 lock washers and 3 8 16 long brass hex head screws needed to secure cables to the ends of...

Page 15: ...The cables should include 3 8 lugs to fit onto the 3 8 posts on the 5 point terminal block iii Size the battery bussing to terminal block wires according to the number of batteries connected in paral...

Page 16: ...ore commissioning CAUTION Turn the inverter s main DC Disconnect on only AFTER ALL the built in circuit breakers in the PHI Battery bank are turned on Refer to the System Commissioning SimpliPhi batte...

Page 17: ...mino Del Sol Oxnard CA 93030 USA 805 640 6700 info simpliphipower com SimpliPhiPower com 15 5 0 Technical Support For technical support related to your BOSS 6 Enclosure please contact us as at 805 640...

Reviews: