Document: LT0400
4100ES-S1 Programming Guide
AS1668 Fan Controls
10-7
10.4.2
LED Configuration
The LEDs configuration couples the Red Amber and Green LEDs of each fan to a pseudo
point.
Each fan uses 4 LEDs:
LED 1 set = Red LED is ON = Fan is running.
LED 2 set = Amber LED is ON = Fan is faulty.
LED 3 set = Green LED is ON = Fan is not running.
LED 4 is not used.
These pseudo points can be monitored via the panel’s display screen and referred to from
the online executable via Custom Controls.
In the
Mode
box
select
‘ON’.
In the
Reference
Address
text
box enter the
address of the
airflow
monitoring
device.
Highlight the next
line to configure
the next entry
with the Fault
pseudo point
(starting at
P1265).
In the
Mode
box
select
‘OFF’.
In the
Reference
Address
text
box enter the
address of the airflow monitoring device.
Every 4
th
line (the 4
th
entry of each fan) should be left as SMPL and without a pseudo
point configured.
When all the configured fans have pseudo points for the
Switch
and
LED
– click OK.
Summary of Contents for 4100ES-S1
Page 1: ...4100ES S1 Fire Indicator Panel Programming Guide Australian Programming Guide LT0400 Issue 1 5...
Page 2: ......
Page 7: ...Document LT0400 4100ES S1 Programming Guide Introduction 1 1 1 Introduction...
Page 10: ...4100ES S1 Programming Guide Document LT0400 Introduction 1 4 THIS PAGE IS INTENTIONALLY BLANK...
Page 11: ...Document LT0400 4100ES S1 Programming Guide System Overview 2 1 2 System Overview...
Page 39: ...Document LT0400 4100ES S1 Programming Guide Adding Zone Displays 7 1 7 Adding Zone Displays...
Page 61: ...Document LT0400 4100ES S1 Programming Guide Custom Control 9 1 9 Custom Control...
Page 69: ...Document LT0400 4100ES S1 Programming Guide AS1668 Fan Controls 10 1 10 AS1668 Fan Controls...
Page 95: ...Document LT0400 4100ES S1 Programming Guide Appendices 12 1 12 Appendices...