4100ES-S1 Programming Guide
Document: LT0400
Adding Expansion Modules
8-12
8.8
Adding 4100-0113 RS-232/2120 Interface Module
The 4100-0113 RS-232/2120 Interface Module provides two RS-232-C outputs (Port A and
Port B) that can be configured for remote printers, CRT, or as a Computer Port for
communications to a remote system (e.g., BMS Systems).
To add the 4100-0113 RS-232/2120 Interface Module to the panel:
Select the
HARDWARE
Tab.
Expand the
Unit 0
, ‘Box 1’ and ‘Bay
2’.
Click on the “
+
” sign beside the
INTERFACE
option on the
Available Hardware
window.
Drag and drop the
4100-0113 RS-
232/2120 Interface
Icon over to the
Bay 2
icon.
The card will be added to the panel
configuration.
Double click on the card and in the
Properties
Tab adjust its address to be
greater than 4, then enter in the
Card
Custom Label:
text box, a descriptive
label.
Set the
Ports
as in the following example
for RS232 connection to PC (used for
generating printed reports). Adjust the
baud rate, etc, if needed.
Summary of Contents for 4100ES-S1
Page 1: ...4100ES S1 Fire Indicator Panel Programming Guide Australian Programming Guide LT0400 Issue 1 5...
Page 2: ......
Page 7: ...Document LT0400 4100ES S1 Programming Guide Introduction 1 1 1 Introduction...
Page 10: ...4100ES S1 Programming Guide Document LT0400 Introduction 1 4 THIS PAGE IS INTENTIONALLY BLANK...
Page 11: ...Document LT0400 4100ES S1 Programming Guide System Overview 2 1 2 System Overview...
Page 39: ...Document LT0400 4100ES S1 Programming Guide Adding Zone Displays 7 1 7 Adding Zone Displays...
Page 61: ...Document LT0400 4100ES S1 Programming Guide Custom Control 9 1 9 Custom Control...
Page 69: ...Document LT0400 4100ES S1 Programming Guide AS1668 Fan Controls 10 1 10 AS1668 Fan Controls...
Page 95: ...Document LT0400 4100ES S1 Programming Guide Appendices 12 1 12 Appendices...