Document: LT0400
4100U-S1 Programming Guide
Creating a Configuration
Issue 1.4
15 December 2010
Page 4-3
CPU in the text entry field labelled „CPU #‟, and then click on the „Update Access Codes‟
button.
If the CPU Serial number is not known then power up the panel - the CPU Serial Number
appears on the initial screens displayed during the panel start-up. If the panel is not
available, leave the CPU serial number empty for now. If you try downloading the
configuration to a panel without entering the serial number, or it is wrong, a warning will be
given but you can still complete the process. Once the number is known, enter it and
download the configuration.
4.3 Adjusting the Number of Zone Displays
To delete unnecessary front panel display zones:
Click the Custom Control tab.
Open Program 4 (labelled as „AS4428 CONTROL LOGIC ZONES 1 - xx‟).
Scroll down to display the last zones‟ equations.
Highlight the equations for the unused zones using the Shift and Down Arrow keys.
Each zone is comprised of 6 custom control equations that are labelled with that zone
number.
Press the „Delete‟ key and then the „y‟ key repeatedly to acknowledge the deletion of
each equation.
4.4 Adding the AZF Logic
The Alarm Zone Facility logic (the custom control equations for the zones) should not need
to be modified unless new hardware is added to the panel, e.g., when extending an existing
4100U-S1 panel with 16 zones to 32 or 64 zones, etc. Note this may require an additional 64
LED/switch controller (4100-1288) and LED/switch modules (4100-1282) to be installed in
the panel. This programming is described in Chapter 7.
4.5 Where to Next?
New systems have to be configured with the addressable devices, and the devices assigned
to zones. This is covered in chapter 5.