4100U-S1 Programming Guide
Document: LT0400
Creating a Configuration
Page 4-2
15 December 2010
Issue 1.4
4.1 Creating a New Project File
This method describes how to create a new 4100U-S1 configuration using the template
configuration file as the starting point. SF0369 contains the zipped template files. These files
should be unzipped to an appropriate folder on your PC such as C:\4100UJOBS. Run the
4100U programmer of the correct version and click on the „File‟ menu and select „Open‟.
Browse to the location containing the 5 default configurations supplied with SF0369:
S1_16ZN.SDB4100U for 16 zones,
S1_32ZN.SDB4100U for 32 zones
S1_64ZN.SDB4100U for 64 zones.
S1_16Z_F.SDB4100U for 16 zones, 8 fans
S1_32Z_F.SDB4100U for 32 zones, 12 fans
Choose the one that has more front panel zones than are required, as it is easier to remove
extra zones rather than add more. Click OK.
All templates have the required Pseudo points and custom control equations for fan controls.
The templates with _F also have hardware preconfigured.
After the file
is opened do a „Save As‟/‟Copy...‟, enter the new job name and click OK. Note
that the „Job Name‟ you enter will show on the front panel when the “
Display Software
Revision Level
” command is entered.
Now proceed with adding and modifying the site specific information as described below.
4.2 Adding Panel Information
Enter the relevant information on the „General Info‟ page in the „Panel‟ tab.
Panel Information
o
Description = Site name.
o
Alternate Description = Site name.
o
Project Number = Software job number (must be obtained from Simplex).
o
Order number = Client
‟s order # for the panel.
o
Agency listing = should always be - CSIRO.
o
NFPA Standard = (not required).
o
Standby Generator = unticked.
o
Hours of standby battery = should be 24, or 72 if not brigade connected.
o
A/C breaker location = (fill in if known).
Branch Information
o
Branch number = (not required).
o
Branch location = Local Simplex office location.
o
Contact = Local Simplex contact name (could be sales person or tech etc).
o
Sales person = Local Simplex sales pers
on‟s name.
o
Project Eng = Name of project engineer (system designer).
o
Technician =
Service technician‟s name (if known).
o
Customer = Building owner (if known).
o
Contractor = Contractor company name.
Programmed by - Appropriate fields to be filled in, i.e., if programmed by Simplex we fill
in branch name file and phone. If programmed by contractor put in local Simplex contact
name (e.g., sales rep).
Hardware lock enable = leave unchecked.
Comment = Further information like panel location.
To enter the panel CP
U serial number click on the „Panel‟ tab, then click on the „Features‟
page. Then tick the „Runtime Enable Edit‟ checkbox. Enter the serial number of the panel