Page 10 of 60
1.1.2.1
Card Missing/Failed
Description:
The circuit card is not communicating correctly with the panel controller.
Possible causes:
Card has not been fitted
Card is not seated correctly on connector
-
Power down panel, clean connectors and reinsert
Card has not been addressed correctly
Card DIP Switch incorrectly set (Dipswitch 1 always in ON position)
Another card has been addressed the same as this card
Card has failed
1.1.2.2
Correct Card Abnormal
Description:
The wrong type of card has been addressed at this location.
Possible causes:
Incorrect card fitted in the panel.
Two cards have the same address.
1.1.2.3
Short Circuit Abnormal
Description:
The addressable loop has a short circuit or the + and – wires are crossed over.
Possible causes:
If there are no isolators fitted or the short is between the panel and the isolator then the loop will stop
operating. This may also display a channel fail
Find the short circuit and fix – disconnect the loop totally, check each pair for a short circuit with a
Multimeter. If fault evident continue these checks at half way points around loop until short is
narrowed down
If short circuit cannot be detected with a Multimeter, disconnect one side of the loop only and
disconnect devices at half way points until the short circuit fault clears, to narrow down the fault
location.
NOTE:
Panel will need to be reset between each disconnection as this fault will latch
Summary of Contents for 4100 Classic
Page 1: ...DIS FNG Simplex Fire Products Fault Assistance Guide...
Page 4: ...1 0 Identifying Simplex 4100 Series Faults...
Page 26: ...Page 25 of 60 2 0 4100 Crash Codes General Information...
Page 35: ...Page 34 of 60 34 of 60 of 60 of 5 of 1 60 4 0 Identifying F3200 Faults...
Page 42: ...Page 41 of 60 41 of 60 of 60 of 5 of 1 60 5 0 Identifying faults on a QE90...
Page 44: ...Page 43 of 60 43 of 60 of 60 of 5 of 1 60 5 2 ECP versions 2 xx 4 xx 6 xx System Fault Display...
Page 55: ...Page 55 of 60 5 10 ECM Networked System System Fault Display...