Point Editing for TrueAlert Device,
Continued
TrueAlert Horn
Appliance Point
Editing
Use this device type to edit TrueAlert Horn appliances. The following editing options are
available for this appliance:
Table 7-14. TrueAlert Horn Point Editing Options
Option
Description
Custom Label
This field can be used to describe the appliance's function, location, or other
descriptive information.
Style
Select the Indoor Style
Coding Type
Select the Coding Type to set the cadence of the audible signal.
System
Default
This sets the coding to the value determined in the System Option tab.
Temporal
A three-pulse coding pattern consisting of three ½ second pulses,
each separated by a ½ second silence. Each three pulse group is
separated by 1 ½ seconds of silence. Pattern repeats until alarm
silence.
March 60
A coded signal that uses 60 beats per minute. Each beat consists of ½
second pulse on, ½ second off. Pattern repeats until alarm silence.
March 120
A coded signal that uses 120 beats per minute. Each beat consists of
¼ second pulse on, ¼ second off. Pattern repeats until alarm silence.
On Steady
On steadily.
Volume
Set the appliance volume:
High
To use this option the appliance's configuration control must be set to
Panel.
Low
To use this option the appliance's configuration control must be set to
Panel.
Note:
The "Copy/Paste/Special Paste" feature can be used to configure multiple devices identically.
Summary of Contents for 4007ES Panels
Page 1: ...4007ES and 4007ES Hybrid Fire Alarm Systems Programmer s Manual 579 1167 Rev D...
Page 2: ......
Page 4: ......
Page 10: ......
Page 18: ......
Page 36: ......
Page 56: ......
Page 122: ...9 38...
Page 132: ......
Page 134: ......
Page 150: ......
Page 166: ...A 16...
Page 167: ......