A-9
4007ES Panel Programmer Manual (
579-1167)
Releasing Specific Controls and Indications,
Continued
Discharge LED
Programming
(RED LED)
Discharge LED Programming (RED LED) is
required for every Hazard Area.
The Discharge LED activates when the suppression release device is in the released state
(solenoid is activated). The LED clears upon system reset or when the solenoid is deactivated.
Below is an example program.
1. Click the
Custom Control
tab.
2. Click the
Suppression Release Wizard
subtab.
3.
Right-click the title (next to the wizard graphic) and select
Properties
to open the Hazard
Area
.
4. Select the
Points
tab and write down the List assigned to
Suppression Dump Points
.
5. Choose an available RED LED on the LED Module located under the
Hardware
tab. Set its
mode as "ON" and set the reference address to the list that was assigned.