13-9
4007ES Panel Programmer Manual (
579-1167)
Adding or Editing Network Information,
Continued
Programming
Central Network
Reset
Note: 1.
Do not reset a Node using Central Network Reset if you cannot see all the alarms associated to
that node. When reset is pressed, P210 goes ON in every node it can reset. If the node where
reset is activated has no alarms, it immediately turns ON the P211 pseudos on all nodes. However
the system in alarm is not ready for this and latches.
2.
If a TSW has a UT connected to it, put P210 of the UT into L0 to reset the UT.
Any 4007ES node can be configured as the Central Network Reset Node. Keep the following
in mind when programming Central Network Reset.
• This application performs separate internal Detector Reset and System Reset.
• All General Alarm Points must be monitored and SMPL-controlled by the Central Node.
• System Points involved:
- P210 Network Detector Reset/L103 External Detector Reset Points
- P211 Network System Reset/L104 External Control Reset Points
Figure 13-9. Central Network Reset
1. Open the network job, using the network programmer. Open the job for the node that will
serve as the Central Reset Node.
2. When the ES Panel programmer appears, click on the
Network
tab at the top of the
programmer. When the Network window appears, click on the
Network Points
subtab at the
bottom of the Network window.
3. Right click in the Network window. When the choices appear, click on
Edit Externals
. A
dialog appears. Click on the drop down list box and choose one of the nodes on the network.
4. Click
OK
to close the dialog. When you do this, a tag list containing the public points from
the selected node appears. Click on
P210
and press the space bar to select the point. Click
P211
and press the space bar to select the point. Click
OK
to close the taglist.
5. Repeat Steps 3 and 4 for every node on the network.
6. Click on the
List
tab at the top of the programmer. When the List window appears, click the
General List
subtab at the bottom of the window. Scroll through the list, right click on L103
and select
Tag List
.
7. Click on the
Filter
icon at the top of the
Tag List
. When the list of choices appears, click the
Network Externals
check box. All of the External Points appear.
8. Click on the entry for
P210
and press the space bar.
9. Repeat Steps 6 through 8 for every node on the network.
10. Click on the
List Tab
at the top of the programmer. When the
List
window appears, click
the
General List
subtab at the bottom of the window. Scroll through the list, right click
L104 and select
Tag List
.
Continued on next page
Summary of Contents for 4007ES Panels
Page 1: ...4007ES and 4007ES Hybrid Fire Alarm Systems Programmer s Manual 579 1167 Rev D...
Page 2: ......
Page 4: ......
Page 10: ......
Page 18: ......
Page 36: ......
Page 56: ......
Page 122: ...9 38...
Page 132: ......
Page 134: ......
Page 150: ......
Page 166: ...A 16...
Page 167: ......