User manual - INDICATOR TRS-10a 

2. 

       GENERAL CHARACTERISTICS

The 

TRS-10a

 wall mounted indicator is designed to display digital values and short,

4-letter messages. This superior system makes the display flicker when a displayed value is

not refreshed.   It is a slave device that communicates with the Master device via RS 485

interface with Modbus RTU protocol. The indicator is dedicated to the TRS system (multipoint

temperature and humidity recording system), but it can cooperate with any superior system

equipped with RS 485 link with Modbus RTU protocol. It has a small plastic casing. 

3. 

       TECHNICAL DATA

Power supply voltage

typically 10 VDC (9 VDC - 12 VDC)

Current consumption

during operation - up to 30 mA

during Modbus transmission - up to 80 mA

Display

LED, 4 digit, 9 mm height, red, high bright

Number of modules in 1 network

maximum 127

Communication interface

Baud rate

RS 485, 8N1 / Modbus RTU

9600 bit/sec.

Data memory

non-volatile memory, EEPROM type

Protection level

IP 65 (ABS casing)

Housing type

Housing material

Housing dimensions (L x W x D)

without glands

with glands

wall mounted

PC

64 x 58 x 35 mm

114 x 58 x 35 mm

Operating temperature

Storage temperature

Altitude

-40°C up to +85°C

-40°C up to +85°C

up to 2000 meters above sea level

Fastening

to wall, 2 M3 bolts

Connection cable

4 conductors (2 supply conductors 

+ 2 data transmission conductors)

Screws tightening max. torque

0,5 Nm

Max. connection leads diameter

2,5 mm

2

EMC

PN-EN 61326:2003

This equipment is not intended for use in residential environments and may
not provide adequate protection to radio reception in such environments. 

Detailed informations about installation of TRS system user can find in:

“User manual for Temperature and Humidity Recording System”

4

Summary of Contents for TRS-10a

Page 1: ...l INDICATOR TRS 10a Firmware v 3 00 or higher Designed for TRS system Read the user s manual carefully before starting to use the unit or software Producer reserves the right to implement changes with...

Page 2: ...6 3 EXAMPLES OF QUERY ANSWER FRAMES 14 7 FORCING OF 0XFF ADDRESS 19 Explanation of symbols used in the manual This symbol denotes especially important guidelines concerning the installation and operat...

Page 3: ...ed off and disconnected from the power supply prior to starting installation of troubleshooting in the case of malfunction Neighbouring and mating equipment must meet the requirements of appropriate s...

Page 4: ...9 mm height red high bright Number of modules in 1 network maximum 127 Communication interface Baud rate RS 485 8N1 Modbus RTU 9600 bit sec Data memory non volatile memory EEPROM type Protection level...

Page 5: ...ducted with a disconnected power supply 4 1 UNPACKING After removing the unit from the protective packaging check for transportation damage Any transportation damage must be immediately reported to th...

Page 6: ...etc Carelessly executed assembly can increase the risk of electric shock Due to possible significant interference in industrial installations appropriate measures assuring correct operation of the uni...

Page 7: ...le in the network must be terminated with 100 150 Ohm resistor Figure 4 4 Connection of the module to the network 7 1 2 3 4 DATA DATA RS 485 Us Us 9 12V DC GND LED indicator force address 0xFF switch...

Page 8: ...nts available to the user Pay attention to the ambient temperature in the room where the unit is operating Excessively high temperatures cause faster ageing of the internal components and shorten the...

Page 9: ...re value out of this range an error occur device answers with exception code 03 improper data value and displayed value will not change After switching power on if display has been set to decimal mode...

Page 10: ...t decade If value 0003h will be written to reg 02h then value 0 124 will be displayed Additionally higher byte of register 02h decides about interpretation of reg 01h value If higher byte of register...

Page 11: ...ower byte of reg 03h as for changes of higer byte of reg 02h Changes of lower byte of reg 03h causes of automatical change of higher byte of reg 02H these two bytes are interdependent If display is in...

Page 12: ...module These addresses can be changed at any time using proper MODBUS commands or can be forced to be reset to 0xFF value using module internal momentary switch to enhance system installation process...

Page 13: ...ying status physical copy of higher byte of 02h register higher byte always 0 Byte mode always 0 can not be written 04h Yes 100h FFFFh Refresh period 05h Yes 00h 01h Operation mode 20h Yes 0h FFh Devi...

Page 14: ...address 1 All values are represent hexadecimal Field description ADDR Device address on Modbus network FUNC Function code REG H L Starting address address of first register to read write Hi and Lo byt...

Page 15: ...A H L CRC L H 01 06 00 20 00 02 09 C1 3 Turning on of decimal mode ADDR FUNC REG H L DATA H L CRC L H 01 06 00 05 00 00 99 CB The answer the same as the message ADDR FUNC REG H L DATA H L CRC L H 01 0...

Page 16: ...nt 6 Changing of decimal point position ADDR FUNC REG H L DATA H L CRC L H 01 06 00 02 00 02 A9 CB The answer the same as the message ADDR FUNC REG H L DATA H L CRC L H 01 06 00 02 00 02 A9 CB Display...

Page 17: ...s the message ADDR FUNC REG H L DATA H L CRC L H 01 06 00 05 00 01 58 0B Display content 10 Displaying of text Port Because in this mode segments are driven directly by bits of register 01h and 02h it...

Page 18: ...H L CRC L H 01 06 00 02 5C 73 50 EF Display content 11 Read of the registers 1 to 5 in one message example of reading a number of registries in one frame ADDR FUNC REG H L DATA H L CRC L H 01 03 00 01...

Page 19: ...s is implemented in Piggy Soft application as network configuration process To force address of device to value 0xFF turn module power supply and wait until it s LED indicator flashes every 10 second...

Page 20: ...SIMEX Sp z o o ul Wielopole 11 80 556 Gda sk Poland tel 48 58 762 07 77 fax 48 58 762 07 70 http www simex pl e mail info simex pl...

Reviews: