User manual - INDICATOR TRS-10a
Display content:
There is no full implementation of the Modbus Protocol in the device. The
functions presented above are available only.
7.
FORCING OF 0
x
FF ADDRESS
New devices has set to Modbus addresses 0xFE. To enhance system installation
process special operation mode has been developed. It allows to force address 0xFF in single
module using internal momentary switch mounted on module mainboard (Figure 4.3).
Additionally this process forces baud rate to standard value 9600 bit/sec. To use this special
mode MASTER controller must to search new devices – devices with address 0xFF. This
process is implemented in Piggy Soft application as network configuration process.
To force address of device to value 0xFF, turn module power supply and wait until it's
LED indicator flashes every 10 second. Next press internal switch button and hold it at least 4
seconds. While button is being pressed LED indicator is turned off until readdressing. After
about 4 seconds LED indicator start to light permanently – it is signal that module address has
been changed to 0xFF – then release switch. At this moment MASTER controller should find
new device and readdress it (to address other than 0xFF). After remote readdressing LED
indicator is being turned off, and starts to flashes again.
Change of the device address from FFh to 01h:
ADDR
FUNC
REG H,L
COUNT H,L
CRC L,H
FF
06
00
20
00
01
5C
1E
The answer is the same as the message.
19