background image

User manual for - INDICATOR SWE-73-T 

6.2. 

 

     DETECTION OF THE PEAK VALUES

The 

SWE-73-T 

controller is equipped with peaks detection function. It can detect a peaks

of the input signal and display their values. Presets connected with this function are placed in

”HOLd” 

menu (see description of 

”HOLd” menu

). The detection of the peak can be done if

the measured signal raises and drops of value at least equal to parameter  

”PEA”

. Detected

peaks   are  displayed   during   the  time   defined   by parameter  

”timE”

.  If  a  new peak   will  be

detected while one is displayed, this new peak will be displayed and display time counter will
be cleared

 

(Figure 6.1). If no peaks are detected while time 

”timE” 

elapses

,

 device starts to

show   the   current   value   of   input   signal   again.  If   „

HdiS

”=”

HOLD

”   then   setting   parameter

"timE"

=

0.0

  causes holding peak value until  

[ESC]

  button is pressed.

 

If „

HdiS

”=”

rEAL

” then

value 

"timE"

=

0.0

 means no holding. Displaying peak value is signalized by flashing most right

decimal point.

Figure 6.1. Process of peaks detection

7. 

       DEVICE PROGRAMMING

The   device   menu   allow   user   to   set   all   parameters   connected   to   operation   of

measurement input, control modes, critical situations behaviour, communication via RS-485

and  access   settings.  The meaning  of  the  particular  parameters  is   described  in  paragraph

MENU DESCRIPTION

.

7.1. 

 

     PROGRAMMING MENU

To enter main menu (being in the measurement mode) operator must to press and hold

at least 2 sec. 

[ESC/MENU] 

button.

If the user password is defined (see parameter 

“Scod“

), operator have to enter correct

one before proceeding to menu options . Entering of the passwords is similar to the edition of
numeric parameters

 

(see: 

PARAMETERS EDITION

 

)

,

 however presently editing digit is showed

only on the display, other digits are replaced by “-” sign.

13

”timE”

measure

time

”timE”

”PEA”

”PEA”

real measurement result
display value

Summary of Contents for SWE-73-T

Page 1: ...Low cost no keyboard Read the user s manual carefully before starting to use the unit or software Producer reserves the right to implement changes without prior notice 2017 06 05 SWE 73 T_INSSXEN_v 2...

Page 2: ...DEVICE PROGRAMMING 13 7 1 PROGRAMMING MENU 13 7 2 PARAMETERS EDITION 14 7 2 1 Numeric parameters digit change mode 14 7 2 2 Numeric parameters slide change mode 14 7 2 3 Switch parameters LIST type 15...

Page 3: ...e connected to PE wire The unit must be properly set up according to the application Incorrect configuration can cause defective operation which can lead to unit damage or an accident If in the case o...

Page 4: ...e SWE 73 T is equipped with RS 485 Modbus RTU communication interface The parameters offset baud rate can be selected while ordering The device can be configured via IR remote controller or optionally...

Page 5: ...to 70 C or 20 C to 70 C Humidity Altitude 5 to 90 no condensation up to 2000 meters above sea level Screws tightening max torque 0 5 Nm Max connection leads diameter 2 5 mm2 Safety requirements accor...

Page 6: ...to the manufacturer Attached with the unit please find user s manual warranty assembly brackets 2 pieces 4 2 ASSEMBLY The unit is designed for mounting inside housings control panel switchboard insuri...

Page 7: ...1 Mounting hole dimensions a recommended b allowable Figure 4 2 Installing of brackets and dimensions of connectors 7 68 mm max 5 mm 32 5 mm max 5 mm 67 mm 32 5 mm 9 mm A 12 mm 10 mm 16 mm 8 5 mm 24V...

Page 8: ...eter must be selected in such a way that in the case of a short circuit of the cable from the side of the unit the cable shall be protected against destruction with an electrical installation fuse Wir...

Page 9: ...tection systems e g RC type Use of screened signal cables is recommended Signal cable screens should be connected to the earthing only at one of the ends of the screened cable In the case of magnetica...

Page 10: ...s possible to avoid of measurement errors Measured value can be corrected constant correction using toFS parameter from menu inPt Due to low precision 2 wire connection is not recommended When 4 or 2...

Page 11: ...internal components and shorten the fault free time of unit operation In cases where the unit gets dirty do not clean with solvents For cleaning use warm water with small amount of detergent or in the...

Page 12: ...er supply on device ID and software version are showed on the display next the controller goes to the measurement mode 6 1 MEASUREMENT MODE In the measure mode the measurement results are displayed on...

Page 13: ...lue until ESC button is pressed If HdiS rEAL then value timE 0 0 means no holding Displaying peak value is signalized by flashing most right decimal point Figure 6 1 Process of peaks detection 7 DEVIC...

Page 14: ...press ENTER 7 2 1 Numeric parameters digit change mode Numerical parameters are displayed as decimal numbers The mode of its new value entering depends on chosen edit method see parameter Edit In mod...

Page 15: ...key ESC after SEt causes in cancelling of made changes and returning to menu Functions of buttons when editing numeric and switching parameters While editing numeric parameter change of current flash...

Page 16: ...menu This menu contains parameters connected with peak detection function See also full description of the peak detection function in paragraph DETECTION OF THE PEAK VALUES modE the type of detected...

Page 17: ...es RS 485 interface baud rate It can be set to one of 8 possible values 1 2 2 4 4 8 9 6 19 2 38 4 57 6 115 2 which respond to the baud rates of 1200 2400 4800 9600 19200 38400 57600 and 115200 bit s r...

Page 18: ...7 3 7 dEFS parameter This setting allows to restore the factory settings of the device To get the access to this option special password is required 5465 next the device displays acknowledge question...

Page 19: ...Aud mbAc rESP modE PEA timE Hdis Parameter edition SEt 4 digit special password entering 0 _ _ _ Default settings restoring Scod MENU ESC ENTER MENU ESC MENU ESC MENU ESC MENU ESC ENTER MENU ESC MENU...

Page 20: ...device parameters and display value are available via RS 485 interface as HOLDING type registers numeric values are given in U2 code of Modbus RTU protocol The registers or groups of the registers can...

Page 21: ...ssion to write registers via RS 485 interface 0 write denied 1 write allowed 25h Yes 0 5 rESP parameter in rS menu additional response delay 0 no additional delay 1 10c option 2 20c option 3 50c optio...

Page 22: ...er 8 3 EXAMPLES OF QUERY ANSWER FRAMES Examples apply for device with address 1 All values are represent hexadecimal Field description ADDR Device address on modbus network FUNC Function code REG H L...

Page 23: ...2 21 F1 DATA identification code 20B2h 3 Change of the device address from 1 to 2 write to reg 20h ADDR FUNC REG H L DATA H L CRC L H 01 06 00 20 00 02 09 C1 DATA H 0 DATA L new device address 2 The a...

Page 24: ...B COUNT L the count of being read registers max 16 The answer ADDR FUNC BYTE C DATA H1 L1 DATA H2 L2 DATA H3 L3 CRC L H 01 03 06 00 0A 00 00 00 01 78 B4 DATA H1 L1 reg 01h 10 displayed value 1 0 DATA...

Page 25: ...bri6 16 Configuration of peaks detection function HOLd menu modE Kind of detected changes norm 16 PEA Minimum detected change 0 0 16 timE Maximum time of peak displaying 0 0 16 HdiS The type of displa...

Page 26: ...Microlectra bv Augustapolder 12 2992 SR Barendrecht The Netherlands www microlectra nl info microlectra nl...

Reviews: