User manual - METER SRT-94-XA
•
If parameter „
AL
” = „
on
”, the relay will be turned on in the critical situations,
even if his parameter
“modE”
=
”noAC”.
7.3.2.
“bEEP” menu
This menu contains options connected with acoustic signal :
"
AL
”
- if this parameter is set to “
on
”, any critical situation causes by acoustic signal
"
r1”
- if this parameter is set to “
on
”, activation of relay
R1
causes by acoustic signal
"
r2
"
- if this parameter is set to “
on
”, activation of relay
R2
causes by acoustic signal
"
r3
"
- if this parameter is set to “
on
”, activation of relay
R3
causes by acoustic signal
"
r4
"
- if this parameter is set to “
on
”, activation of relay
R4
causes by acoustic signal
Acoustic signal (turned on by e.g. relay ) can be turned off by pressing of any
button
7.3.3.
“inPt” menu
This menu presets the measurement input:
“
tYPE
"
- type of the input / sensor. This parameter can be set to values:
thermocouple type
measurement range
”
tc K
”
-200˚C ÷ +1370˚C
”
tc S
”
-50 ˚C ÷ +1768˚C
”
tc J
”
-210˚C ÷ +1200˚C
”
tc t
”
-200˚C ÷ +400˚C
”
tc n
”
-200˚C ÷ +1300˚C
”
tc r
”
-50 ˚C ÷ +1768˚C
”
tc b
”
+250˚C ÷ +1820˚C
”
tc E
”
-200˚C ÷ +1000˚C
”
volt
”
The device has additional measurement range (-10÷90mV)
mainly for diagnostics of measurement circuits. Being in
this range, unit displays direct voltage connected to its
input with resolution 0.01mV (without compensation of
cold ends).
”FiLt”
- this parameter sets filtration rate. It can be set to values from 0 (no filtration ) to 5
(strongest filtration – time window about 2 sec).
“toFS”
- offset (expressed in 1°C, range ± 99°C.). This parameter allows shifting of
measurement scale, and express value added to calculated (measured) result.
Warning: The offseting of a scale is realised independently of cold ends automatic
compensation.