7.1.
DIP SWITCH SETTINGS
All connections must be made while power supply is disconnected!
Turn OFF the unit before changing the DIP switch settings. Any changes in
the DIP switch settings will not take effect until the unit is switched OFF
then powered ON. Default of DIP switch is all OFF.
Figure 7.1. DIP switch description
7.1.1.
DP1 Input type
is equipped with one measuring input. The are following types to be
selected:
•
Contact, for low speed signals
•
Open collector
•
Voltage, high speed
12
INPUT MODE
COUNT SPEED
COUNT MODE
OUTPUT TIME
OPERATION MODE
DP4 & DP5 ENABLE
RESET TIME
KEY PROTECT ENABLE
CONTACT/OPEN COLLECTOR INPUT
LOW SPEED (30 Hz)
ADD/SU BTRACT INPUT
HOLD
OVER RUN
DISABLE
DISABLE
VOLTAGE INPUT
HIGH SPEED (1 kHz , 5 kHz, 10 kHz)
QUADRATURE INPUT
AUTO_RESET
ENABLE
ENABLE
OFF
ON
DP1
DP2
DP3
DP4
100 ms
DP5
DP7
20 ms
2 ms
DP8
DP6
Operation m ode and
Output time can be set
simply