background image

User manual for - TIMER SLC-94 

6.2. 

 

 CONTROL OF RELAY OUTPUTS

 

 

Controlling of external devices up on 

main timer

 and totalizer values is possible  thanks 

to build in relay outputs. The operation principle of relay output is defined   by parameters: 

SEtP

”, “

modE

”, “

Src

”.

Parameter  “

SEtP

 

defines the  

threshold

  of an relay.  Setting of threshold is made by 

entering values of parameters  “

Hr

”, “

min

”, “

SEc

”, “

mSEc

”. Note, that the sum of all of these 

parameters decides what is exact threshold value. 

Example 1:

Setting   “

Hr

”=2, “

min

”=30, “

SEc

”=40, “

mSEc

”=567  causes that relay will be activated after 2 

hours , 30 minutes, 40 seconds and  567 milliseconds.

Example 2:

Setting  “

Hr

”  =1,  “

min

”  = 65 ,  “

SEc

”=0,  “

mSEc

”=0 causes that relay will be activated after 2 

hours and 5 minutes .

While   controlling   process   relay   output   can   change   its   state   to  

active  

only  after   the 

counter reach its threshold value.  Active state of the relay (closed or opened) is defined by 
parameter “

modE

”.  The selection of controlling counter (main timer or totalizer) is realised  by 

parameter 

“Src

”.

The   action   related   to  

threshold   value

  is   not   immediate.   Maximum   delay 

( activation or deactivation while controlled by main timer ) is less than 12 ms for OC 

outputs and up to 20ms for electromechanical relays.

If  

“Src”  

parameter equals  

“total”

  then  “

mSEc

” parameter in relay threshold edition menu 

(“

SEtP1

” 

i

 “

SetP2

”)  is non active and equals zero.

All  parameters  connected   with   relay outputs   are  described   in  paragraph  

”rEL1”  

and 

”rEL2” menu

.

7. 

   DEVICE PROGRAMMING

 

 

The device menu allow user to set all parameters connected to operation of counting 

input, reset source, displaying format, communication via RS-485 and access settings. The 
meaning of the particular parameters is described in paragraph 

MENU DESCRIPTION

.

7.1. 

 

 PROGRAMMING MENU

 

 

 To enter main menu (being in the measurement mode) operator must to press and hold  

at least 2 sec. 

[ESC/MENU] 

button. 

16

i

Summary of Contents for SLC-94

Page 1: ...4 Firmware v 1 12 or higher Input type pulse Function of time counting and totalizer Read the user s manual carefully before starting to use the unit or software Producer reserves the right to impleme...

Page 2: ...ch parameters LIST type 18 7 2 MENU DESCRIPTION 19 7 2 1 rELAy1 rELAy2 menu 19 7 2 2 StArt parameter 20 7 2 3 StoP parameter 20 7 2 4 rESEt parameter 20 7 2 5 Menu diSPL 20 7 2 6 PuSH menu 21 7 2 7 rS...

Page 3: ...t be properly set up according to the application Incorrect configuration can cause defective operation which can lead to unit damage or an accident If in the case of a unit malfunction there is a ris...

Page 4: ...hen unused In addition the measure can be started stopped and cleared using local keyboard on front of the device or via RS 485 interface Apart from basic function of time counting totalizer is also a...

Page 5: ...IP 65 from front after using waterproof cover IP 40 from front IP 20 housing and connection clips Housing type Housing material Housing dimensions Panel cutout Assembly depth Panel thickness panel NO...

Page 6: ...the requirements listed in the technical data All installation works must be conducted with a disconnected power supply Protecting the power supply clamps against unauthorized persons must be taken in...

Page 7: ...ing into consideration Figure 4 1 4 2 Place the unit in the mounting hole inserting it from the front side of the panel and then fix it using the brackets Figure 4 3 The minimum distances between the...

Page 8: ...ternal fuse or power supply circuit breaker Because of this an external time delay cut out fuse with minimal possible nominal current value must be used recommended bipolar max 2A and a power supply c...

Page 9: ...stallations appropriate measures assuring correct operation of the unit must be applied To avoid the unit of improper indications keep recommendations listed below Avoid common parallel leading of sig...

Page 10: ...on means that depending on device version particular terminal can be marked according to the top or bottom number Figure 4 6 Terminals description relay outputs Description of input terminals START co...

Page 11: ...ditional suppression circuit typically capacitor 47nF min 250VAC in series with 100R 5W resistor connected in parallel to relay terminals or better directly on the load In consequence of using the sup...

Page 12: ...d contacts of external switch while current flow is equal to active state marked Hi of the input and open contacts no current inactive state marked Lo a b Figure 4 10 Example of input terminals connec...

Page 13: ...it gets dirty do not clean with solvents For cleaning use warm water with small amount of detergent or in the case of more significant contamination ethyl or isopropyl alcohol Using any other agents c...

Page 14: ...isplay next the controller goes to the counting mode and displays timer main or totalizer which were showed before power down 6 1 COUNTING MODE In counting mode the result of main timer or totalizer i...

Page 15: ...while Baud 9 600 and rESP Std equals about 14ms The delay can be calculated using formula tD min 10 000 13 rESP bAud miliseconds tDmin minimum delay for rESP Std use rESP 0 The functions of keyboard...

Page 16: ...s threshold value Active state of the relay closed or opened is defined by parameter modE The selection of controlling counter main timer or totalizer is realised by parameter Src The action related t...

Page 17: ...u is displayed if the name of some parameter is displayed enter the edition of this parameter present value of the parameter is displayed ESC MENU button allow user to exit present menu level and goes...

Page 18: ...be described as a sets of values a lists out of which only one of the options available on the list can be selected for the given parameter Options of switching parameter are selected using v keys Sh...

Page 19: ...threshold value is edited by all parameters below together Hr hours range 0 99 999 min minutes range 0 999 999 SEc seconds range 0 999 999 mSEc milliseconds range 0 999 999 the sum of all of these pa...

Page 20: ...ising edge from low to high state stops counting Hi Lo falling edge from high to low state stops counting Examples are shown in paragraph 8 on page 25 7 2 4 rESEt parameter This parameter defines the...

Page 21: ...min sec millisec 100 milliseconds h m S 0 00 00 00 99 59 59 max 100hour hour min sec 1 second h m do not concern 0 00 00 0 9999 59 max godz hour min 1 minute h h 10 do not concern 00 00 00 99999 9 max...

Page 22: ...wer of the device received and sent via RS 485 interface Modbus protocol defines minimum delay between frames to 3 5 chars Internal RISC processor of SLC 94 allows get very fast responses This additio...

Page 23: ...d parameter The one use password can be used one time only it is impossible to use it again The one use password can be restored by Service Division only 7 2 10 Edit t parameter This parameter allows...

Page 24: ...ENTER SEtcod Parameter edition ENTER MENU ESC ENTER mbACCE rESP Parameter edition ENTER MENU ESC ENTER ENTER MENU ESC Addr bAud Parameter edition MENU ESC rESEt MENU ESC rELAy2 MENU ESC MENU ESC rELA...

Page 25: ...unter can be done exclusively using external signal START Other possibilities are blocked Clearing of the counter Clearing of main counter and totalizer can be made in one of following ways using exte...

Page 26: ...ars counter asynchronously 8 2 EXAMPLE 2 CONTROLLING BY STATE OF START LINE Settings StArt Hi rESEt Lo Hi Counting runs while high level occurs on START line Low state on this line stops counting None...

Page 27: ...ng cleared after writing of bit 2 in control register 0Ch via RS 485 interface Clearing of totalizer occurs after bit 3 in control register 0Ch is set 27 START Hi RESET Lo Hi counter value content of...

Page 28: ...processes BROADCAST queries but then do not send any answers 9 1 LIST OF REGISTERS Register Write Range Register description 01h No 02h No 0 FFFFFFFF Main timer value higher word Main timer value low...

Page 29: ...d 5 38400 baud 6 57600 baud 7 115200 baud 23h4 Yes 0 1 mbAccE parameter in rS 485 menu permission to write registers via RS 485 interface 0 write denied 1 write allowed 25h Yes 0 5 rESP parameter in r...

Page 30: ...higher word 47h Yes see descr Parameter mSEC of rELAy2 submenu lower word Joined value of registers 46h 47h from 0 to 999 999 48h Yes 0 2 Parameter modE 2 of rELAy2 relay mode 0 tryb noAct 1 mode on 2...

Page 31: ...re represent hexadecimal Field description ADDR Device address on Modbus network FUNC Function code REG H L Starting address address of first register to read write Hi and Lo byte COUNT H L No of regi...

Page 32: ...format to h m S hours minutes seconds milliceconds ADDR FUNC REG H L DATA H L CRC L H 01 06 00 09 00 01 98 08 The answer the same as the message ADDR FUNC REG H L DATA H L CRC L H 01 06 00 09 00 01 9...

Page 33: ...L CRC L H 01 06 00 0A 00 04 A8 0B DATA L written value out of permissible range here 00h lub 01h Answer of the device with error code included 03h ADDR FUNC ERR CRC L H 01 86 03 02 61 There is no ful...

Page 34: ...ration PuSH Enable disable control of the counter with local keyboard oFF 21 Parameters of relay R1 operation rEL1 menu SEtP1 Relay1 threshold 0 19 modE1 Relay1 mode noAct 19 Src1 Relay1 control sourc...

Page 35: ...User manual for TIMER SLC 94 35...

Page 36: ...SIMEX Sp z o o ul Wielopole 7 80 556 Gda sk Poland tel 48 58 762 07 77 fax 48 58 762 07 70 http www simex pl e mail info simex pl...

Reviews: