User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
3.
TECHNICAL DATA
Power supply voltage
(depending on version)
External Fuse (required)
Power consumption
85...
230
...260V AC/DC; 50 ÷ 60 Hz
or 19...
24
...50V DC; 16V...
24
...35V AC
T - type, max. 2 A
typically 15 VA; max. 20 VA
Display (depending on version)
3.5” or 5.7”, TFT color graphic display, 320 x 240
pixels, with LED backlight
Sensor power supply output
24V DC ± 5% / max. 200 mA,
Basic communication interfaces
RS 485, 8N1/2, Modbus RTU, 1200 bit/s ÷ 115200 bit/s
USB Host port, USB Device port
Digital i
nput
1 input 0/15..24V DC,
galvanic isolation (low state:
0÷1V, high state:8÷24V)
power consumption
: 7,5 mA / 24V,
isolation: 1min @ 500V DC.
Optional communication module*
Second USB Host port
Serial RS-485 and RS-485/RS-232
Ethernet 10M RJ-45
Optional input modules*
4/8/16/24x Voltage (0÷10V) / Current (0÷20mA)**
16/24x NTC (0÷100k)/ Voltage (0÷10V)/
Current (0÷20mA)/ Digital (TTL,HTL)**
6x Isolated current (4÷20mA),
4/6x RTD (Pt100, Pt500, Pt1000, Cu50, Cu100)**
4/8x/12 TC (J, K, S, T, N, R, E, L(GOST), B, C**
8/16/24x Digital input**
3/5x Universal input**
2/4x Universal counter input**
2/4x Hourmeter module**
2/4x Flo 2/4x Current input**
2/4x Pulse input + 2/4x Current input**
Optional output modules*
4/6x Relay 5A/250V
(cos
ϕ
= 1)
**
8/12x Relay 1A/250V
(cos
ϕ
= 1)
**
8/16/24x SSR driver (10
÷
15V, up to 100mA per
output)**
2/4/6/8x IO Passive current output (4
÷20mA)**
Protection level
USB interface on rear panel
USB interface from front
IP 65 (from front, after using waterproof frame)
IP 54 (from front, with transparent door)
IP 40 (from front, standard)
IP 20 (housing and connection clips)
IP 54 (from front, with transparent door)
IP 40 (from front, standard)
IP 20 (housing and connection clips)
Housing type
Housing material
panel
NORYL - GFN2S E1
9