Sime super mk.ii Installation And Servicing Instructions Download Page 8

2.1

STATUTORY REQUIREMENTS

GAS  SAFETY  (INSTALLATION  AND  USE)  REGULATIONS  (as
amended). It is the law that all gas appliances are installed by
a  registered  person,  in  accordance  with  the  above  regula-
tions. Failure to install appliances correctly could lead to pros-
ecution. It is in your own interest, and that of safety, to ensure
that the law is complied with.
In  addition  to  the  above  regulations,  this  appliance  must  be
installed  in  accordance  with  the  current  IEE  Wiring
Regulations  (BS  7671),  Local  Building  Regulations,  the
Building  Standards  (Scotland)  (Consolidation)  Regulations,
Byelaws of the local water undertaking, and Health and Safety
Document No 635 ‘The Electricity at Work Regulations 1989’.
It should also be in accordance with the relevant recommen-
dations  in  the  current  editions  of  the  following  British
Standards  and  Codes  of  Practice:  BS5449,  BS5546,
BS5440:1,  BS5440:2,  BS6798,  BS6891,  and  BG.DM2,
BS7074, and BS5482 for propane installations.

Manufacturer’s instructions must NOT be taken in any way
as over-riding statutory obligations.

2.2

BOILER POSITION

In siting the combination boiler, the following limitations MUST
be observed:
– The boiler is not suitable for external installation. The posi-

tion selected for installation should be within the building,
unless  otherwise  protected  by  a  suitable  enclosure,  and
MUST allow adequate space for installation, servicing, and
operation of the appliance, and for air circulation around it
(section 2.4).

– This position MUST allow for a suitable flue termination to

be made. The combination boiler must be installed on a flat
vertical  wall  which  is  capable  of  supporting  the  weight  of
the appliance, and any ancillary equipment.

– If the combination boiler is to be fitted in a timber framed

building it should be fitted in accordance with the Institute
of Gas Engineers document for Gas Installations In Timber
Frame Housing, Reference 16E/UP/7: 1998. If in doubt,
advice must be sought from the gas supplier

– If the appliance is installed in a room containing a bath or

shower, any electrical switch or control utilising mains elec-
tricity must be so situated that it cannot be touched by a
person using the bath or shower. Attention is drawn to the
requirements of the current I.E.E. Wiring Regulations (BS
7671),  and  in  Scotland  the  electrical  provisions  of  the
Building Regulations applicable in Scotland.

– A  compartment  used  to  enclose  the  appliance  MUST  be

designed and constructed specifically for this purpose. An
existing cupboard, or compartment, may be used provided
it is modified accordingly.

– Where  installation  will  be  in  an  unusual  location,  special

procedures  may  be  necessary.  BS6798  gives  detailed
guidance on this aspect.

2.3

FLUE TERMINAL POSITION

Detailed  recommendations  for  flue  installation  are  given  in
BS5440:1. The following notes are for general guidance:
– The  boiler  MUST  be  installed  so  that  the  terminal  is

exposed to the external air.

– It is important that the position of the terminal allows free

passage of air across it at all times.

– It  is  ESSENTIAL  TO  ENSURE,  in  practice  that  products  of

combustion discharging from the terminal cannot re-enter
the building, or any other adjacent building, through venti-
lators,  windows,  doors,  other  sources  of  natural  air  infil-
tration,  or  forced  ventilation/air  conditioning.  If  this  does
occur,  the  appliance  MUST  be  turned  OFF  IMMEDIATELY
and the gas supplier consulted.

– The minimum acceptable dimensions from the terminal to

obstructions and ventilation openings are specified in fig. 3.

– If  the  terminal  discharges  into  a  pathway  or  passageway

check  that  combustion  products  will  not  cause  nuisance
and that the terminal will not obstruct the passageway.

– Where the lowest part of the terminal is fitted less than 2

m  (78  in)  above  ground,  above  a  balcony  or  above  a  flat
roof to which people have access, the terminal MUST be

4

2

GENERAL REQUIREMENTS FOR INSTALLATION

Terminal position

Directly below an openable window, air
vent or any other ventilation opening
Below guttering, drain pipes or soil pipes
Below eaves, balconies or carport roof
From vertical drain pipes or soil pipes
From internal or external corners
Above  adjacent  ground,  roof  or  bal-
cony level
From a surface facing the terminal
From a terminal facing the terminal
From  an  opening  in  the  carport  (eg
door, window into dwelling)
Vertically  from  a  terminal  on  the
same wall
Horizontally  from  a  terminal  on  the
same wall
Adjacent to opening

A

B
C/D
E
F
G

H
I
J

K

L

M

Minimum spacing

300 mm

12 in

75 mm

3 in

200 mm

8 in

75 mm 

3 in

300 mm

12 in

300 mm

12 in

600 mm

24 in

1,200 mm

48 in

1,200 mm

48 in

1,500 mm  60 in

300 mm

12 in

300 mm  12 in

TABLE 5

Fig. 3

Summary of Contents for super mk.ii

Page 1: ...Super Mk II Installation and servicing instructions GB ...

Page 2: ...ill be made for a service visit where the fault is not due to a manufacturing defect Has a correct by pass been fitted and adjusted Has the system and boiler been flushed Is the system and boiler full of water and the correct pressure showing on the pressure gauge Is the Auto Air Vent open Has the pump been rotated manually Is the gas supply working pressure correct Is the boiler wired correctly S...

Page 3: ... 7 3 INSTALLING THE BOILER 3 1 UNPACKING THE BOILER 8 3 2 FIXING THE BOILER MOUNTING FRAME 3 3 WATER CONNECTIONS 9 3 4 HANGING THE BOILER 3 5 FLUE AND TERMINAL PREPARATION 3 6 FLUE AND TERMINAL INSTALLATION 10 3 7 SEPARATE DUCTS 11 3 8 GAS CONNECTIONS 13 3 9 SAFETY VALVE CONNECTION 3 10 WIRING INSTRUCTIONS 3 11 TIME CLOCK INSTRUCTIONS 14 4 COMMISSIONING AND TESTING 4 1 FILLING THE WATER SYSTEM 14 ...

Page 4: ...USTION CHAMBER INSULATION 8 3 FAN ASSEMBLY 8 4 MAIN BURNER 8 5 IGNITION DETECTION ELECTRODES 8 6 GAS VALVE 23 8 7 AIR PRESSURE SWITCH 8 8 LIMIT THERMOSTAT 8 9 OVERHEAT THERMOSTAT 8 10 THERMISTOR 24 8 11 IGNITION CONTROL BOX 8 12 DRIVER PCB 8 13 PUMP 8 14 D H W HEAT EXCHANGER 8 15 DIVERTOR VALVE COMPLETE 8 16 DIVERTOR VALVE MICROSWITCH ASSEMBLY 8 17 C H EXPANSION VESSEL 8 18 PRESSURE GAUGE 25 8 19 ...

Page 5: ...ate flues kit see section 3 for details The boiler is designed for use with sealed primary water sys tems and is supplied fully assembled and equipped with com plete valve packs If the wall thickness is less than 0 5 m 19 in the appliance can be installed from inside the room without access to the external wall although a wall liner is required This is available as an optional extra and full detai...

Page 6: ...NG RANGE 10 5 35 700 13 5 46 200 2 4 1 0 12 5 42 600 15 9 54 200 3 8 1 5 14 5 49 500 18 2 62 200 5 1 2 0 16 5 56 400 20 6 70 200 6 4 2 6 18 5 63 300 22 9 78 200 7 7 3 1 X 20 6 70 200 25 3 86 200 9 0 3 6 22 6 77 100 27 6 94 200 10 3 4 1 24 6 84 000 29 9 102 200 11 6 4 6 26 6 90 900 32 3 110 200 12 6 5 1 DOMESTIC HOT WATER Max 26 6 90 900 32 3 110 200 12 6 5 1 Min 10 5 35 700 13 5 46 200 2 4 1 0 Dif...

Page 7: ...valve with charging 7 NTC sensor 8 100 C safety thermostat 9 Air relief valve 10 Circulation pump 11 Expansion vessel 12 Safety valve 13 Drain plug 14 Manometer 15 Automatic by pass 16 D H W filter 17 C H return cock 18 C H flow cock 19 D H W cock 20 Gas cock 21 Limit thermostat 22 Frost stat 23 Non return valve Fig 2 ...

Page 8: ...he current I E E Wiring Regulations BS 7671 and in Scotland the electrical provisions of the Building Regulations applicable in Scotland A compartment used to enclose the appliance MUST be designed and constructed specifically for this purpose An existing cupboard or compartment may be used provided it is modified accordingly Where installation will be in an unusual location special procedures may...

Page 9: ...PVC insulated cable NOT LESS than 0 75 mm2 24 x 0 2 mm to BS6500 Table 16 Wiring external to the boiler MUST be in accordance with current l E E Wiring Regulations BS 7671 and local regulations The supply connection to the flying lead provided MUST be made to a fused double pole switch having a 3 mm 1 8 in contact separation in both poles serving only the boiler and system controls The fuse rating...

Page 10: ...uld be fitted as shown above Take note of the requirements relative to container capacity height above system inclusion of a non return valve stop cock and automatic air vent in the feed pipe as shown in fig 5 Note also the feed pipe connection is made to the heating return as close to the appliance as possible The Local Water Undertaking MUST approve ALL connections between the system and a water...

Page 11: ...nection The final 600 mm 24 in of the mains supply pipe to the boiler must be copper A maximum D H W flow rate of 10 3 l m 2 3 gpm 13 l m 2 9 gpm for Super 105 Mk II is recommended Higher flow rates will not damage the appliance but may lower the water temperature below an acceptable level If the appliance is installed in an area where the temporary hardness of the water supply is high say over 15...

Page 12: ... section 2 2 and the requirements for flue position section 2 3 and minimum clearances Table 2 are satisfied These minimum clearances are essential to provide access for servicing For the rear flue application fix the flue template 14 to the frame with the selftapping screws provided Mark the position of the two upper installation frame fixing holes the two lower frame fixing holes and the flue ai...

Page 13: ...ember locates onto the installation frame Screw the adjusting screws 15 fig 7 until the appliance is secure and vertical Connect the isolation valves to the boiler using the gaskets provided 3 5 FLUE AND TERMINAL PREPARATION If the wall thickness is less than 0 5 m 19 in the flue air duct may be fitted without access to the outside wall providing that the optional wall liner kit is used This consi...

Page 14: ...an 1 m 3 6 1 Installations from inside the room Wall thicknesses up to 0 5 m 19 in only Hole diameter suffi cient to accept wall liner 130 mm 5 1 4 in if optional kit is used A wall liner 127 mm 5 in internal diameter 500 mm 19 in long is available as an optional extra for use when fitting the flue air duct from inside the building or where it is required to seal the hole through a cavity wall Cut...

Page 15: ...re that the silicon seal on the fan outlet correctly engages and forms a seal at its joint with the elbow This must be checked from inside the sealed chamber Secure the elbow onto the top of the appliance using the four screws and washers provided and refit the sealed chamber front panel 3 7 SEPARATE DUCTS Optional alternative twin pipe system When installing the separate ducts comply with the req...

Page 16: ...nction n 5 code 8092700 120 ø 80 160 KEY 1 Sponge rubber gasket ø125 95 2 Fixing screw 3 Air smokes flow splitting unit with take off point 4 Sectors diaphragm ø 38 Fig 14 Fig 15 Fig 16 Example of allowable installation calculation Super 90 Mk II model in that the sum of the head losses of the single fittings is less than 9 00 mm H2O Intake Outlet 7 meter horizontal pipe ø 80 x 0 20 1 40 7 meter v...

Page 17: ...ted in the valve and extend the pipe to ensure that any discharge from the safety valve is safely routed to a drain The discharge pipe should be a minimum of 15 mm copper and should avoid sharp corners or upward pipe runs where water may be retained 3 10 WIRING INSTRUCTIONS Refer to sections 2 6 2 7 and fig 19 The external wiring is connected to the boiler via a lead cable situated behind the cont...

Page 18: ... Ensure that the rotary switch on the facia panel is set to the SUMMER position D H W Only turn the D H W ther mostat to maximum fully clockwise and turn on the electri cal supply Fully open any D H W tap and the burner will light Allow the boiler to run for at least 5 minutes and check that the burner pressure is as stated in section 1 3 The D H W burner pressure is factory set and should not req...

Page 19: ... an acceptable D H W temperature To set the D H W flow procede as follows select Summer position and turn the D H W ther mostat to max fully open the D H W tap furthest from the boiler check that the boiler is firing at maximum burner pressure adjust the D H W flowrate by turning the restrictor lever on the divertor valve until a D H W temperature rise of approx 35 C is achieved This corresponds t...

Page 20: ...old by disconnecting the four screws Inspect and if necessary clean the injectors electrodes and the main burner bars 5 2 FAN ASSEMBLY Disconnect the electrical connections to the fan Note the position of the earth conductor 16 the installer should Give the Users Instructions to the householder and emphasise their responsibilities under the Gas Safety Installation and Use Regulations 1996 as amend...

Page 21: ...iagrams section 7 to earth pin on plug Resistance should be less than 1 Ω ohm If the resistance is greater than 1 Ω ohm check all earth wires for continuity and all contacts are clean and tight If the resistance to earth is still greater than 1 Ω ohm then this should be investigated further 6 2 SHORT CIRCUIT CHECK Switches turned FULL ON meter set on Ω ohms x 1 scale Test leads from L to N on appl...

Page 22: ... Replace the pump Check pump connection Set right the contacts Is there continuity between power terminals of PCB control board and PCB ignition Is sensor OK Check gap between the ignition electrode and hood check if the electrode lead and fit are not damaged Does it now spark Is there 230V AC available between 11 and 4 terminals and between 11 and 10 terminals of PCB ignition Replace the PCB cont...

Page 23: ... connection Clean or replace filter at inlet of divertor valve Set right the contacts Replace fuse F1 Is there continuity between power terminals of PCB control board and PCB ignition Is sensor OK Replace sensor Is there 230V AC available between 11 and 4 terminals and between 11 and 10 terminals of PCB ignition Replace the PCB control board Is there 230V AC available at the fan terminal Replace t...

Page 24: ...ectrode ER Detection electrode A SIT 503 control box TS 100 C safety thermostat OP Time clock PF Air pressure switch V Fan P Circulation pump VP Divertor valve TAG Frost thermostat C Rotary switch TA Room thermostat M Modulator SM C H sensor TL Limit thermostat F1 Fuse Note The room thermostat must be connected to the terminals 22 23 20 Fig 25 ...

Page 25: ...Gas valve with control box 4 D H W exchager 6 Combustion chamber 7 Water gas exchager 10 100 C safety thermostat 11 NTC sensor 12 Limit thermostat 13 Air relief valve 14 Circulating pump 15 Fan 16 Smoke pressure switch 17 Frost stat Fig 26 Super 105 Mk II model ...

Page 26: ...ion panels followed by the rear panel re assemble in reverse order refill and recommission the system as described in section 4 8 3 FAN ASSEMBLY Remove the casing front panel and sealed chamber front panel as described in section 5 1 Disconnect the electrical connections to the fan Note the position of the earth conductor Unscrew the four screws securing the fan mounting plate Drop and tilt the fa...

Page 27: ...ectly set by turning on and off the D H W inlet valve several times and ensuring that the pressure returns to that pre viously adjusted Isolate the power supply re connect the modulation lead restore the power and re check the maximum pressure then re fit the plastic cover 1 Reduce the D H W draw off rate to the minimum neces sary to maintain the burner alight by carefully adjusting the D H W Inle...

Page 28: ...he D H W circuit by opening any D H W tap below the level of the boiler Remove the two screws pivot the control box downwards Disconnect all union connections to the D H W heat exchanger and remove the heat exchanger Fit new heat exchanger and re assemble in reverse order using the new gaskets supplied with the heat exchanger Refill and re commission the system as described in section 4 1 8 15 DIV...

Page 29: ...nd re assemble in reverse order Refill and re commission the system as described in section 4 1 8 20 AUTOMATIC AIR VENT Remove the casing front panel as described in section 5 1 Isolate the C H flow and return valves 17 18 fig 2 Drain the appliance through the drain point 13 fig 2 Unscrew the automatic air vent Fit the new automatic air vent using a suitable jointing com pound and re assemble in r...

Page 30: ...t Ø 12x18x2 51 6226403 O ring 2031 52 6017211 Manual air vent 1 4 53 6040201 Pressure relief valve 54 6124803 Myson CP51AS pump 1 90 54 A 6124810 Myson CP61AS pump 1 105 55 6013100 Automatic air vent 3 8 56 2030229 Gasket Ø 22x30x2 Position Code Description Model 57 6264812 C H return pipe 90 57 A 6264822 C H return pipe 105 58 6264712 C H flow pipe 90 58 A 6264721 C H flow pipe 105 59 6146700 Lim...

Page 31: ...ressure nipple 90 33 6229209 Fan mounting plate 90 33 A 6229210 Fan mounting plate 105 34 6225615 Fan 90 34 A 6225613 Fan with venturi 105 Position Code Description Model 35 6139606 Combustion chamber front panel 90 35 A 6139608 Combustion chamber front panel 105 36 6139754 Combustion chamber front insulation 90 36 A 6139756 Combustion chamber front insulation 105 37 6229101 Smoke pressure switch ...

Page 32: ...19571 Lower closing panel 74 6272910 Control panel 75 6044022 Gem 76 6217003 Temperature and pressure gauge 77 6197707 Time programmer 78 6230679 Control board 79 6201501 Trimmer spindle Ø 5 80 6201502 Trimmer spindle Ø 6 Position Code Description Model 81 6260701 Rotary switch 82 2211610 Earth faston 83 6273010 Control panel protecting cover 84 6273110 Room stat connection cover 85 6230921 Knob Ø...

Page 33: ...nd in depth technical training courses FREE LUNCH Certificate on completion of the course Please fill in the form below for more details Combination Boilers Name Address Postcode Tel No Company Please hand this slip to your local merchant or return it to SIME HEATING products UK ltd Jubilee Works Middlecroft Road Staveley Chesterfield Derbyshire S 43 3XN Tel 01246 471950 Fax 01246 281822 ...

Page 34: ... n g p ro d u c t s u k l t d Jubilee Works Middlecroft Road Staveley Chesterfield Derbyshire S 43 3XN Tel 01246 471950 Fax 01246 281822 For service enquiries and boiler faults contact our service company on Tel 01246 470777 Fax 01246 470094 ...

Reviews: