Faults / Solutions
Here below you can find some causes and the possible solutions
for some problems that could cause a failure to start or a bad
working of the burner.
A fault usually makes the lock-out lamp light which is situated in-
side the reset button of the control box.
When lock out lamp lights the burner will attempt to light only after
pushing the reset button. After this if the burner functions correct-
ly, the lock-out can be attributed to a temporary fault.
If however the lock out continues the cause must be determined
and the solution found.
Tab. E
7
Faults / Solutions
Faults
Possible causes
Solution
The burner will not start when
the limit thermostat closes
Lack of electrical supply
Check presence of voltage in the L - N clamps of the
control box
Check the conditions of the fuses
Check that safety thermostat limit is not lock out
The flame sensor sees false light
Eliminate the light
Resistance or start thermostats are faulty
Replace them
The connections in the control box are wrong-
ly inserted
Check and connect completely all the plugs
Burner runs normally in the
prepurge and ignition cycle
and locks out after 5 seconds
ca.
The flame sensor is dirty
Clear it
The flame sensor is defective
Change it
Flame moves away or fails
Check pressure and output of the fuel
Check air output
Change nozzle
Check the coil of solenoid valve
Burner starts with an ignition
delay
The ignition electrodes are wrongly posi-
tioned
Adjust them according to the instructions of this man-
ual
Air output is too high
Set the air output
Nozzle dirty or worn
Replace it
WARNING
The manufacturer cannot accept responsibility for
any damage to persons, animals or property due
to error in installation or in the burner adjustment,
or due to improper or unreasonable use or non
observance of the technical instruction enclosed
with the burner, or due to the intervention of un-
qualified personnel.