34
007-6419-002
5: Chassis Maintenance
Replacing Disk Drives
Caution:
Except for short periods of time while swapping hard drives, do not operate the server
with the hard drive slots empty.
The server has twenty-four hot-swappable 2.5" drive bays. The hard drives are mounted in drive
carriers to simplify their installation and removal from the chassis. System power may remain on
when removing carriers with drives installed. These carriers also help promote proper airflow for
the drive bays. For this reason, even empty carriers without drives installed must remain in the
chassis.
Removing Carrier from Chassis and Drive from Carrier
Use the following procedure to remove the HDD carrier from the chassis and the drive from the
carrier.
1.
Press the release button on the drive carrier.
This extends the drive carrier handle. See
2.
Using the handle, pull the drive carrier out of the chassis.
3.
Remove the disk drive or dummy drive from the carrier.
See
Summary of Contents for UV 30
Page 1: ...SGI UV 30 System User Guide 007 6419 002 ...
Page 4: ......
Page 8: ......
Page 10: ......
Page 12: ......
Page 21: ...Serverboard Features 007 6419 002 5 Figure 1 4 Serverboard Block Diagram ...
Page 33: ...Install the System into a Rack 007 6419 002 17 Figure 3 2 Installing the Inner Rails ...
Page 37: ...Check the Serverboard Setup 007 6419 002 21 Figure 3 4 Accessing the Inside of the Chassis ...
Page 49: ...Replacing a Power Supply 007 6419 002 33 Figure 5 3 Replacing a Power Supply ...
Page 51: ...Replacing Disk Drives 007 6419 002 35 Figure 5 4 Removing HDD Carrier from Chassis ...
Page 52: ...36 007 6419 002 5 Chassis Maintenance Figure 5 5 Removing Dummy Drive from Carrier ...
Page 55: ...Replacing System Fans 007 6419 002 39 Figure 5 7 System Fans ...
Page 56: ......
Page 64: ......
Page 66: ......