Table A-5
Environmental Specifications (Single E-Rack)
Feature
Specification
Temperature tolerance
(operating with 95-Watt
processors)
+5
C (41
F) to +35
C (95
F) (up to 1500 m / 5000 ft.)
+5
C (41
F) to +30
C (86
F) (1500 m to 3000 m /5000 ft. to 10,000 ft.)
Temperature tolerance
(operating with 135-Watt
processors)
+5
C (41
F) to +28
C (82.4
F) (up to 1500 m / 5000 ft.)
+5
C (41
F) to +23
C (73.4
F) (1500 m to 3000 m /5000 ft. to 10,000 ft.)
Temperature tolerance
(non-operating)
-40
C (-40
F) to +60
C (140
F)
Relative humidity
10% to 95% operating (no condensation)
10% to 95% non-operating (no condensation)
Rack cooling requirements
Chilled water cooling
Heat rejection (dissipation)
to air
Zero BTUs
Heat rejection (dissipation)
to water
Approximately 246 kBTU/hr maximum (21 tons) (based on 100%
dissipation to water)
Maximum altitude
10,000 ft. (3,049 m) operating
40,000 ft. (12,195 m) non-operating
E-Cell rack acoustical noise
level (sound power)
Approximately 80 dBA (at front of system)
Optional cooling distribution
rack (CDU) acoustical noise
level (sound power)
Approximately 65 dBA (at front of unit)
System-level Specifications
007-6399-002
69
Summary of Contents for ICE XA
Page 1: ...SGI ICE XA System Hardware User Guide Document Number 007 6399 002 ...
Page 4: ......
Page 12: ......
Page 25: ...Powering the System On and Off 007 6399 002 7 Figure 1 4 Three Phase PDU Example ...
Page 32: ......
Page 65: ...SGI ICE XA Series D Rack 42U 007 6399 002 47 Figure 4 1 D Rack Front Lock Example ...
Page 72: ...54 007 6399 002 4 Rack Information Figure 4 4 E Cell Rack Assembly Example CDU on Left ...
Page 82: ......