PS-DA Manual Pull Station

Patented, U.S. Patent No. Des. 428,351; 6,380,846; Other Patents Pending

Document 52155 

I56-2831-001

Description

The PS-DA pull station is a non-coded, dual-action manual pull station with a key-lock reset 

feature. It provides Silent Knight control panels with one normally open (N/O) alarm initi-

ating input. The PS-DA meets the ADAAG controls and operating mechanisms guidelines 

(section 4.1.3[13]), and the ADA requirement for a 5 lb. maximum pull force to activate 

the pull station. Operating instructions are molded into the pull station handle along with 

Braille text. Molded Terminal numbers are also present.

Ratings 

Switch contact (N/O) is gold plated for reliability and rated at 0.25 A at 30 volts (AC or DC).

Installation

The PS-DA pull station can be surface mounted to an SB-10 or SB-I/O surface backbox or 

semi-flush mounted on a standard single-gang, double-gang or 4˝ (10.16 cm) square electrical 

box. The optional BG-TR trim ring can be used if the PS-DA is to be semi-flush mounted.

Operation

To activate the dual-action pull station, push in and pull down on the handle. The word 

‘ACTIVATED’ appears after the handle is pulled down. This will remain until the pull sta-

tion is reset.
The pull station includes one Single Pole, Single Throw (SPST) Normally Open (N/O) 

switch which closes upon activation of the pull station.

Resetting the Pull Station

1.   Insert the key into the lock and rotate 1/4 turn counterclockwise.

2.   Open the door until the handle returns to normal.

3.  Close and lock the door.

NOTE:

 Closing the door automatically resets the switch to the ‘Normal’ position. Opening 

the door will not activate or deactivate the alarm switch.

CAUTION!

Do not detach the door of the pull station during installation. The door of the pull station 

cannot be reattached to the backplate after the backplate has already been installed onto an 

electrical box.

P0260-00

STRIP GAUGE

1        2       3      4

IDC –

FROM  

FACP +

TO NEXT

DEVICE

– IDC

+

WARNING: DO NOT LOOP WIRING 

UNDER ANY TERMINALS. BREAK WIRE 

RUN TO MAINTAIN IDC SUPERVISION.

P0205-00

Wiring

CAUTION!

Install  the  Silent  Knight  PS-DA  pull  station  in  accordance  with  these  instructions,  

applicable NFPA standards, national and local Fire and Electrical codes and the requirements 

of the AHJ (Authority Having Jurisdiction). Regular testing of the devices should be conduct-

ed in accordance with the appropriate NFPA standards. Failure to follow these directions may 

result in failure of the device to report an alarm condition. Silent Knight is not responsible for  

devices that have been improperly installed, tested or maintained.

ADA Compliance

For ADA compliance, if the clear floor space only allows forward approach to an object, the 

maximum forward reach height allowed is 48 inches (121.92 cm). If the clear floor space 

allows parallel approach by a person in a wheelchair, the maximum side reach allowed is 

54 inches (137.16 cm).

PS-DA

Manual Pull Station

WARNING!

  Do not loop wiring under any 

terminals. Break wire run to 

maintain IDC supervision.

Document 52155 

I56-2831-001

12 Clintonville Road

Northford, CT 06472

203-484-7161

Fax: 203-484-7118

www.silentknight.com

 

©

2009 Honeywell International Inc. 

06/09 