Programming
151430
9-15
9.5
Point
You may need to change characteristics of individual input points (detectors and switches)
even after using JumpStart AutoProgramming. This section explains how to change options
for: type of input point; latching/non-latching status (switches); and name and zone
assignment of a point.
9.5.1
Point Programming For 5815XL Module
To program for an 5815XL Module points, follow these steps:
1. Enter the installer code. The panel will automatically go to the main menu.
2. Select
for Panel Programming.
Display reads:
Initializing
Please wait . . .
3. Press
to enter point menu.
4. Press the
or
arrows to select the desired module. Refer to Section 8.5 Quick Refer-
ence Table for available choices.
5. Press .
6. Select S for sensor for M for module.
7. Enter the number of the point you wish to edit.
8. Press .
9. Select the type of device by pressing
or
arrows. Refer to Table 9-2 under column
heading “Type Selection” for a list of choices.
Table 9-2 Programming Options for 5815XL Modules
Type
Selection
Function
Latching Option
Comments
UNUSED
select for SLC points that are unused
DETECTOR
PHOTO
spot photoelectric detectors
ION
spot ionization detector
HEAT
spot heat detector
PHOT DUCT
duct photoelectric detector
Acclimate
acclimate photoelectric detector
Heat HT
high temperature heat detector
Photo-Heat
photoelectric detector with heat sensor
Beam
beam smoke detector
7
4
Summary of Contents for IFP-2000
Page 2: ......
Page 12: ...IFP 2000 Installation Manual viii...
Page 22: ...IFP 2000 Installation Manual 1 10 151430...
Page 26: ...IFP 2000 Installation Manual 2 4 151430...
Page 31: ...Before You Begin Installing 151430 3 5 Figure 3 1 Wire Routing Example...
Page 100: ...IFP 2000 Installation Manual 5 14 151430...
Page 194: ...IFP 2000 Installation Manual 10 20 151430...
Page 210: ...IFP 2000 Installation Manual 12 8 151430...
Page 230: ...IFP 2000 Installation Manual A 14...
Page 232: ...IFP 2000 Installation Manual B 2 151430...
Page 236: ......
Page 237: ......