PROFINET™
AP20S
Date: 24.08.2020
Art. No. 89992
Mod. status 133/20
Page 72 of 79
5
PROFINET™
5.1
Description
The position indicator has been designed as CIP Generic Device (Type 2Bh).
5.1.1
IP- Configuration
After completing the settings, reset (soft boot) is required to ensure that
the changed configuration is adopted.
The station name and IP configuration can be reset to factory default using
).
The IP configuration is assigned to the parameter class N.
The IP configuration of the position indicator can be performed via the network or the display
menu.
The selection in the menu
chPARA
\
SETEPN
\
SET ID
determines the station name
to be used.
The selection in the
chPARA
\
SETEPN
\
SET NW
menu determines the setting that
will be used.
Display
Description
NETWRK
The setting is via the network (factory setting).
DEVICE
The setting is via the display menu.
With the factory setting, the IP configuration is done automatically via a DHCP server in the
network. The following basic setting applies:
Station name
""(empty)
IP address
0.0.0.0
Subnet mask
0.0.0.0
Gateway
0.0.0.0
DHCP
Enabled
If the station name is set via the displays menu (DEVICE selection), the station name will be
generated according to the following pattern:
"siko-ap20s-yyy" yyy = set value of ID in decimal notation
In the basic setting, the value of ID=124. This results in the station name "siko-ap20s-124".
The setting of ID=8 results in the station name "siko-ap20s-008".
If IP configuration is via the display menu (DEVICE selection), the following basic setting
applies:
IP address
192.168.1.124
Subnet mask
255.255.255.0
Gateway
192.168.1.1
DHCP
Disabled