background image

1. Disconnect AC power before servicing.

7. Do not let power cords touch hot surfaces.

2. Refer to wiring diagram for proper connections.

8. Mount and secure the fixture at a location and height 

3. All servicing should be performed by qualified personnel.

    to avoid ready access  and tampering by unauthorized 

4. Consult your local building code for approved wiring and 

    persons.

    installation.

9. The use of accessory equipment is not recommended by

5. Do not use outdoors.

    the manufacturer and may cause an unsafe condition.

6. Do not use this equipment for other than intended use.

IMPORTANT SAFEGUARDS READ AND FOLLOW ALL SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS

HORIZONTAL MOUNT SINGLE FACE

DOUBLE FACE

MASTER

REMOTE

CLASS 2 LOW VOLTAGE WIRING 18-22 AWG

STANDARD 

4" x 4" J- BOX 

STANDARD 

4" x 4" J- BOX 

STANDARD 

4" x 4" J- BOX 

STANDARD 

4" x 4" J- BOX 

24 VDC

INPUT

12 1/8"

VERTICAL MOUNT SINGLE FACE

8 1/4"

24 VDC

INPUT

STANDARD 

4" x 4" J-BOX

STANDARD 

4" x 4" J-BOX

Fig. 1

J-BOX INSTALLATION

1.

See Fig 1: Install a 4” x 4" J-box for Master sign and a 4” x 4" J-box for Remote sign. Position J-boxes approx ¼” 

              below finished panel surface and set in line, 12 1/8” apart for horizontal mount, and 8 ¼” apart for vertical mount. 
              NOTE- Location of J- boxes must be accurate to position the two signs correctly.   

2.

See Fig 2: Attach low voltage input and output wiring to Terminal Block mounted on Master power supply assembly 
(some fixtures may be shipped with wiring in place). Maintain color codes and polarities as shown. 

MASTER

REMOTE

CLASS 2 LOW VOLTAGE WIRING 18-22 AWG

24 VDC

INPUT

12 1/8"

Series RAE-REC

Installation Instructions & Users Manual

Rapier Accessible Exit Sign

Remote From Central Battery System Series CBS

12.13.00

J-BOX

PUSH- WIRE

TERMINAL BLOCK

G

24 VDC 
INPUT
CIRCUIT

24 VDC 
OUTPUT
CIRCUIT

G

G

G

W

W

R

W

W

R

B

B

Fig. 2

MASTER SIGN ASSEMBLY

KEY

G- GREEN: COMMON GND: 24 VDC NEG
W- WHITE: EXITS AND CVRE: 12-24 VDC POS
R- RED: EMERGENCY: 24VDC POS
B- BLACK: SECURITY / NIGHT OPS: 24 VDC POS

ALL MODELS
EMERGENCY POWER RATING (EPR): 
SINGLE FACE- 4 WATTS
DOUBLE FACE- 8 WATTS

Reviews: