1. Disconnect AC power before servicing.
2. Refer to wiring diagram for proper connections.
3. All servicing should be performed by qualified personnel.
4. Consult your local building code for approved wiring and installation.
5. Do not use this equipment for other than intended use.
6. Do not let power cords touch hot surfaces.
7. Mount and secure the fixture at a location and height to avoid ready access
and tampering by unauthorized persons.
8. The use of accessory equipment is not recommended by the manufacturer
and may cause an unsafe condition.
9. Suitable for wet locations. See product label for temperature limitations.
IMPORTANT SAFEGUARDS READ AND FOLLOW ALL SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
PIGTAIL
BL R
B
LOW VOLTAGE
SUPPLY WIRING
MULLION
TOP MOUNT
(OPTION)
SIDE MOUNT
BRANCH CIRCUIT
INPUT/ OUTPUT 24 VDC
WIRING THROUGH
MULLION AWG #16 - 20
MUE
J-
BOX
SUITABLE FOR WET LOCATIONS
AMBIENT TEMPERATURE LIMITS:
Standard "BB" models: -20º C to +40º C
Remote models: -40º C to +50º C
KEY
B- BLACK: COMMON: 12/24 VDC NEG -
R- RED: EMERGENCY: 24VDC POS +
BL- BLUE: SECURITY/ NIGHT LIGHTING: 24 VDC POS +
LED Mullion Mount Emergency Light
Remote Series MUE-RE
Moonlite LED
™
Emergency & Security Light
REV 04.17.04
INSTALLATION INSTRUCTIONS AND OWNER'S MANUAL
(2) # 8-32 x 1/2
CANOPY MOUNT
SCREW
POLARIZED
CONNECTOR
(2) # 6-32 x 3/8
SET SCREW
LAMP
HOUSING
BUSH
BASE
GASKET
1
WIRE ACCESS 5/8" DIA
BASE MOUNT
POSITION
2 1/2"
(2) #6-32 X 3/8
SET SCREW
(2) DIA 5/32" MOUNT
SCREW LOCATIONS
ROTATE TO
FINAL POSITION
Fig. 1
2 3/4"
1 3/8"
Fixture Assembly
1. See Fig 1. Drill 5/8" dia wire access hole and (2) 5/32" dia (or suitable tapping size) mount screw holes in the mullion beam
at center of selected fixture location.
2. Route low voltage supply wiring through mullion and attach lamp plug pigtail (supplied) to supply wiring with wire nuts.
MAINTAIN COLOR CODES AT CONNECTOR: RED Positive, BLACK Negative.
3. Loosen (2) #6-32 set screws, release lamp housing from base and rotate lamp housing about 90° to expose mount screw
holes. Attach polarized lamp plug on pigtail, insert wiring and lamp plug into mullion, and attach base to mullion with (2) #8
screws (not supplied). Tighten evenly on gasket.
4. Rotate lamp housing to fit base and secure with (2) set screws. Turn AC power ON with battery connected at the RPS or
central battery system, press the PUSH TO TEST button to check operation. Full battery charge requires 24 hrs.