SIGNALTEC GmbH, Reutersbrunnenstrasse 27, D-90429 Nürnberg, GERMANY, T. +49 911 2550993-0, F. +49 911 2550993-13, Email[email protected]Web: www.signaltec.com

 

 

 
 
 

TPS II 
Single Channel Current Transducer System 
 

Installation Manual 

 

 

Summary of Contents for CT 100

Page 1: ...1 2021 SIGNALTEC GmbH Reutersbrunnenstrasse 27 D 90429 Nürnberg GERMANY T 49 911 2550993 0 F 49 911 2550993 13 Email info signaltec com Web www signaltec com TPS II Single Channel Current Transducer System Installation Manual ...

Page 2: ...tput module to the voltage input terminals of a multimeter 4 Operating instructions 5 Scaling 5 1 Current output ratio 5 2 Sensor output ratio when using the passive plug on resistors 5 3 Sensor output ratio when using the active plug on voltage amplifiers 6 Status readout interface 6 1 Pin out of the 25 pole D SUB 7 Specifications 7 1 TPS rack 7 2 Transducers 7 3 Connection cables 7 3 1 Standard ...

Page 3: ...vily overloaded Power and transducer status are visible on the front panel The information of the status readout interface on the back panel can be used to switch off the primary current via a relay or a PLC in case the transducer is overloaded the TPS is switched off or the output loop is interrupted All these events will change the transducer status to error on the front panel led and the status...

Page 4: ...the TPS rack with the delivered D SUB current transducer connection cable The transducer output current can be connected directly to the current input terminals of a current or a power meter with 4 mm safety leads 3 2 Connection of the optional plug on voltage output module to the voltage input terminals of a multimeter The current transducer will be connected to the TPS rack with the delivered D ...

Page 5: ... and the output current loop is closed An unpowered transducer can be damaged as well as a sensor with open current output loop The power and transducer status ok or error overload are visible on the front panel and available on the status readout interface see chapter 6 Power LED off TPS system switched off Power LED green TPS switched on Status LED off TPS system switched off Status LED green Tr...

Page 6: ...2 Sensor output ratio when using the passive plug on resistors Transducer Range DC RMS CF 2 Standard Burden Resistor Ratio Scaling Factor CT 100 100 A MCTS BR10 0 01 100 A 2000 mV 20 mV A CT 200 200 A MCTS BR10 0 01 200 A 2000 mV 10 mV A CT 400 400 A MCTS BR3 75 0 01 400 A 1000 mV 2 5 mV A CT 500 500 A MCTS BR1 5 0 02 500 A 1000 mV 2 mV A CT 1000 1000 A MCTS BR1 5 0 02 1000 A 1000 mV 1 mV A CT 200...

Page 7: ... read out via the Status Readout Interface The interface gives out the transducer status by means of potential free relay contacts Switching voltage 200 V Switching current 2 A Transducer status ok TPS on and transducer in normal range Transducer status error TPS off transducer in over range or current output loop open 6 1 Pin out of the 25 pole D SUB Status Pin Connection Wire Color ok 14 2 green...

Page 8: ... Mass 181 mm 87 2 mm 2 HU 250 mm 2 7 kg General Data Operation Temperature Operation Humidity Warranty period 10 60 C 20 90 RH noncondensing 36 Months Electrical Data Supply voltage Output voltages Max Power Consumption 100 240 VAC 50 60 Hz fused with 6 A slow blow 15 VDC 3 4 Amax 15 VDC 2 0 Amax The maximum power consumption depends on the current consumption of each transducer The maximum power ...

Page 9: ...0 0008 0 00115 0 0012 0 0012 Temp Coefficient of MR 0 2 ppm K 0 2 ppm K 0 1 ppm K 1 ppm K 0 3 ppm K 0 1 ppm K Frequency Influence 3 of MV 0 01 kHz 0 01 kHz 0 015 kHz 0 01 kHz 0 05 kHz 0 075 kHz Angular Accuracy 0 015 kHz 0 015 kHz 0 015 kHz 0 015 kHz 0 05 kHz 0 075 kHz Temperature Range 40 85 C 40 85 C 40 85 C 40 85 C 40 85 C 40 85 C Test Voltage 50 Hz 4 95 kV 4 95 kV 4 95 kV 4 2 kV 4 2 kV 6 kV In...

Page 10: ...NALTEC GmbH Reutersbrunnenstrasse 27 D 90429 Nürnberg GERMANY T 49 911 2550993 0 F 49 911 2550993 13 Email info signaltec com Web www signaltec com Dimensions Transducers CT 100 CT 200 CT 400 Transducers CT 500 CT 1000 Transducer CT 2000 ...

Page 11: ...CTS TPS 20 20 m 0 34 mm 1 05 Ω 4 19 Ω 1 58 kg MCTS TPS 2 5 0 75 2 5 m 0 75 mm 0 06 Ω 0 24 Ω 0 37 kg MCTS TPS 5 0 75 5 m 0 75 mm 0 12 Ω 0 47 Ω 0 65 kg MCTS TPS 10 0 75 10 m 0 75 mm 0 24 Ω 0 95 Ω 1 15 kg MCTS TPS 15 0 75 15 m 0 75 mm 0 36 Ω 1 42 Ω 1 70 kg MCTS TPS 20 0 75 20 m 0 75 mm 0 47 Ω 1 90 Ω 2 30 kg MCTS TPS 25 0 75 20 m 0 75 mm 0 59 Ω 2 37 Ω 2 80 kg MCTS TPS 30 0 75 30 m 0 75 mm 0 71 Ω 2 85 ...

Page 12: ...ombinations Dimensions Transducer Passive BR Scaling Output Voltage Width Height Depth Mass 51 mm 51 mm 62 mm connectors included 85 g CT 100 MCTS BR10 0 01 20 mV A 2 Vrms 100 Arms CT 200 MCTS BR10 0 01 10 mV A 2 Vrms 200 Arms CT 400 MCTS BR3 75 0 02 2 5 mV A 1 Vrms 400 Arms CT 500 MCTS BR1 5 0 02 2 mV A 1 Vrms 500 Arms CT 1000 MCTS BR1 5 0 02 1 mV A 1 Vrms 1000 Arms CT 2000 MCTS BR1 0 02 0 5 mV A...

Page 13: ...550993 0 F 49 911 2550993 13 Email info signaltec com Web www signaltec com 8 Switching off and deinstallation Before you switch off the TPS rack open the output current loop or remove any cable between rack and sensor make sure that the primary current is switched off An unpowered transducer can be damaged ...

Page 14: ...rrying bag for rack transducers cables and burden modules TSC Transducer soft case for use with carrying bag TSC1 for CT 100 CT 200 CT 400 TSC2 for CT 500 CT 1000 TSC4 for CT 2000 TPS ROC 18 pole D SUB cable for status readout interface length 3 m BNC4A BNC to 4 mm banana plug adapter BPL0 5 4 mm banana plug test lead set length 0 5 m BPL01 4 mm banana plug test lead set length 1 m BNCL1 BNC to BN...

Reviews: