![SIGMATEK SCP 211 Operating Manual Download Page 19](http://html1.mh-extra.com/html/sigmatek/scp-211/scp-211_operating-manual_1268149019.webp)
S-DIAS Safety CPU Module
SCP 211
11.10.2021
Page 17
5.1
Status LEDs
The LED display lights continuously to indicate that the in- and outputs are active.
Run
green
Run
Indicates
-
The time-limited (LED "S" on) operation mode or
-
or unlimited time ("S" LED off) operation mode.
Module
Status
yellow
status
-
Lights permanently: the module is in service mode
-
Slow blinking frequency: the module is currently in
Idle or Check Configuration mode (distribution of
the configuration)
Error
red
Error
-
Lights permanently: the module is in error mode
-
Slow blinking frequency: the maximum age has
been exceeded for a removed input (can be read
with the SAFETYDesigner )
-
Fast blinking frequency: serious error;
communication with the module is no longer
possible (CANNOT be read with the
SAFETYDesigner )
B
red
Display validation button S1
See chapter "Validation Button" for description
C1
yellow
Command 1
See chapter "Validation Button" for description
C2
yellow
Command 2
See chapter "Validation Button" for description
C3
yellow
Command 3
See chapter "Validation Button" for description
Safety
interface
inactive
yellow
Safety interface connection
Indicates an active Safety interface
DC OK
green
DC OK +24 V
Signals the availability of the supply voltage
Summary of Contents for SCP 211
Page 15: ...S DIAS Safety CPU Module SCP 211 11 10 2021 Page 13 ...
Page 17: ...S DIAS Safety CPU Module SCP 211 11 10 2021 Page 15 4 Mechanical Dimensions ...
Page 35: ...S DIAS Safety CPU Module SCP 211 11 10 2021 Page 33 a b c distances in mm inches ...
Page 38: ...SCP 211 S DIAS SAFETY CPU MODULE Page 36 11 10 2021 ...