![SIGMATEK SCP 211 Operating Manual Download Page 16](http://html1.mh-extra.com/html/sigmatek/scp-211/scp-211_operating-manual_1268149016.webp)
SCP 211
S-DIAS SAFETY CPU-MODULE
Page 14
11.10.2021
3.3
Miscellaneous
Article number
20-890-211
Hardware version
1.x
Approvals
CE, TÜV EG type tested
3.4
Environmental Conditions
Storage temperature
-20 ... +85 °C
Environmental temperature
0 ... +60 °C
Humidity
0-95 %, non-condensing
Installation altitude above sea
level
0-2000 m without derating
> 2000 m up to a maximum of 5000 m with derating of the maximum
environmental temperature by 0.5 °C per 100 m
Operating conditions
pollution degree 2
indoor use only
EMC resistance
in accordance with 61000-6-7:2015 (Generic standards
– immunity
requirements for equipment designed to perform functions in safety-based
systems (functional safety) at industrial facilities)
according to EN 61000-6-2:2007 (industrial area)
(increased requirements in accordance with IEC 62061)
EMC noise generation
in accordance with EN 61000-6-4:2007 (industrial area)
Vibration resistance
EN 60068-2-6
3.5 mm from 5-8.4 Hz
1 g from 8.4-150 Hz
Shock resistance
EN 60068-2-27
15 g
Protection type
EN 60529
IP20
Summary of Contents for SCP 211
Page 15: ...S DIAS Safety CPU Module SCP 211 11 10 2021 Page 13 ...
Page 17: ...S DIAS Safety CPU Module SCP 211 11 10 2021 Page 15 4 Mechanical Dimensions ...
Page 35: ...S DIAS Safety CPU Module SCP 211 11 10 2021 Page 33 a b c distances in mm inches ...
Page 38: ...SCP 211 S DIAS SAFETY CPU MODULE Page 36 11 10 2021 ...