MDP 102-1
Page 38
29.08.2019
t
t
t
t
t
t
t
t
24V
–
Auxiliary
supply
Amplifier drive
ready
“
Main con tact
L1, L2, L3
Interm. circuit
voltage
Main voltage
“
Mains applied
”
Power output
stage
„
enable
“
t
t
t
t
Max. 7 min
Max. 15 s
~ 0V.7 s
t
t
Signal
“
Under voltage
“
Under voltage
threshold
3.3.9 Turn on/off response of the servo amplifier
The turn on/off response of the servo amplifier is shown below.
5 seconds after turning on the 24 V auxiliary supply (start time of the micro controller), the
"Drive ready" signal is set to high.
The above image shows when the 24 V auxiliary supply activates the system through
turning on the main switch and the main supply is engaged later.
This, however, is not absolutely necessary. The main supply can also be activated with
the 24 V auxiliary supply at the same time.
Since the memory of the servo amplifier is volatile, received parameters must be stored in
the host controller. The advantage here lies in the automatic download of program data
when an amplifier is changed.
If the main supply is turned on, the capacitors in the intermediate circuit are charged. This
requires approximately 0.7 seconds.
If the main supply is turned off, the current of intermediate circuit is maintained and can
be used for controlled braking of the motor. If the motor is slowed, the energy is returned
to the intermediate circuit.
If the motor is stopped, the "enable" signal can be removed. After 7 minutes, the interme-
diate circuit is discharged.
Summary of Contents for MDD 111-1
Page 4: ...MDP 102 1 Page 4 29 08 2019 1 1 Components of a servo system...
Page 13: ...MDP 102 1 29 08 2019 Page 13 2 6 Nameplate...
Page 27: ...MDP 102 1 29 08 2019 Page 27...
Page 28: ...MDP 102 1 Page 28 29 08 2019 Connector layout of X1 X2 X3 X4 and X6...
Page 48: ...MDP 102 1 Page 48 29 08 2019...
Page 50: ...MDP 102 1 Page 50 29 08 2019...
Page 84: ...MDP 102 1 Page 84 29 08 2019...