ETV 1591-H
CONTROL PANEL
Page 26
24.03.2015
5.5.2
Named-Pipe Write Function
Functions Overview
Configuration of the SigmatekUpsMonitor Windows service monitor:
Name
Request-ID
Description
ESetShutdownTime
0x80
Sets the time from the main supply failure to the automatic
shutdown of Windows.
Default: 20 seconds
ESetComPort
0x81
Sets the serial interface for the UPS.
Default: \\.\COM1
EEnableAutoShutdown
0x82
Enable/disable the automatic Windows shutdown.
Default: Enabled.
ESetCableType
0x83
Sets the battery extension cable type used.
Default: Type 0 (battery connected directly)
EResetBatteryExchangeNeeded
0xC0
Resets the "Battery exchange needed" warning from the Pipe
read function "EGetBatteryExchangeNeeded".
ESetShutdownTime
Description
Request-ID
Instruction Sequence
Sets the "UPS active time" until
the automatic Windows shut-
down.
0x80
Open connection
Send 4-byte Request-ID (0x80) to Pipe
Send 4-byte "UPS active" time in seconds until shutdown
Read 1-byte (boolean) answer
Close connection
Answer
ByteNo.
Data
type
Info
1
BOOL
FALSE = Error
TRUE = The shutdown time was set in the configuration