CONTROL PANEL
ETV 1591-H
24.03.2015
Page 21
EGetUpsStateInfo
Description
Request-ID
Instruction Sequence
Read UPS information
*Status bytes
*Measurement values
0x03
Open connection
Send 4-byte Request-ID (0x03) to Pipe
Read 19-byte (struct sUpsStateInfo) answer
Close connection
Answer
ByteNo.
Data
type
Info
1
BOOL
Status: Valid flag
FALSE = Data invalid
TRUE = Data valid
2
BYTE
Status byte "battery info", see next page for details
3
BYTE
Status byte "UPS info", see next page for details
4-5
WORD
not used
6-7
WORD
not used
8-9
WORD
not used
10-11
WORD
Measurement value: Actual battery
voltage
Conversion factor: 100 d = 1 V
Value range +10.15 V
+25.09 V
Accuracy: ±0.06 V
Byte sequence: Little Endian
Updating: every second
12-13
WORD
Measurement value: Battery volt-
age under test load (load = 3 A)
Conversion factor: 100 d = 1 V
Value range +10.15 V
+25.09 V
Accuracy: ±0.06 V
Byte sequence: Little Endian
Updating: while the battery is charging: every 60
seconds
14..15
WORD
Measurement value: Actual load
current in the battery
Conversion factor: 1 d = 10 mA
Value range 0 mA
140 mA
Accuracy: ±10 mA
Byte sequence: Little Endian
Updating: every second
16-17
WORD
Measurement value: Actual dis-
charge current from the battery
Conversion factor: 100 d = 1 A
Value range 0 A
13.68 A
Accuracy: ±0.06 A
Byte sequence: Little Endian
Updating: every second
18-19
WORD
not used