BUILD-IN TOUCH TERMINAL 

ETT 775 

 

15.07.2020 

Page 31 

27 

OP PROG 

The  operating  system  is  currently  being 
reprogrammed. 

Info

 

28 

OP INSTALLED 

The  operating  system  has  been  rein-
stalled. 

Info

 

29 

OS TOO LONG 

The operating system cannot be loaded; 
too little memory. 

Restart, report error to  
SIGMATEK.

 

30 

NO OPERATING 
SYSTEM 

Boot loader message. 

No operating system found in RAM. 

Restart, report error to  
SIGMATEK. 

31 

SEARCH FOR OS 

The  boot  loader  is  searching  for  the 
operating system in RAM. 

Restart, report error to  
SIGMATEK. 

32 

NO DEVICE 

Reserved 

 

33 

UNUSED CODE 

Reserved 

 

34 

MEM ERROR 

The  operating  system  loaded  does  not 
match the hardware configuration. 

Solution: 

Use the correct operating 

system version 

35 

MAX IO 

Reserved 

 

36 

MODULE 

LOAD 

ERROR 

The LASAL Module or project cannot be 
loaded. 

Solution: 

Recompile and download the 

entire project 

37 

BOOTIMAGE 

FAIL-

URE 

A  general  error  has  occurred  while 
loading the operating system. 

Contact SIGMATEK 

38 

APPLMEM ERROR 

An  error  has  occurred  in  the  application 
memory (user heap). 

Solution: 

Correct allocated memory 

access error 

39 

OFFLINE 

This error does not occur in the control. 

This error code is used in the 
programming system to show 
that there is no connection to the 
control. 

40 

APPL LOAD 

Reserved 

 

41 

APPL SAVE 

Reserved 

 

44 

VARAN MANAGER 
ERROR 

An  error  number  was  entered  in  the 
VARAN  manager  and  stopped  the 
program. 

Solution: 

Read LogFile 

45 

VARAN ERROR 

A  required  VARAN  client  was  discon-
nected  or  a  communication  error  has 
occurred. 

Solution: 

Read LogFile 

Error Tree 

Summary of Contents for ETT 775

Page 1: ...ETT 775 Build in Touch Terminal Operating Manual Date of creation 22 07 2019 Version date 15 07 2020 Article number 01 230 775 E...

Page 2: ...rved No part of this work may be reproduced edited using an electronic system duplicated or dis tributed in any form print photocopy microfilm or in any other process without express permission We res...

Page 3: ...the input medium for process data and parameters The output is shown on a 7 WVGA TFT color display With the LSE visualization tool graphics can be created on the PC then stored and dis played on the...

Page 4: ...5 1 5 Environmental Conditions 6 1 6 Display 7 WVGA incl Touch 6 1 7 Miscellaneous 7 2 Mechanical Dimensions 8 3 Connector Layout 9 3 1 Front 9 3 1 1 Status LEDs 10 3 2 Rear 11 3 2 1 Applicable Connec...

Page 5: ...Interface Connections 21 7 5 RS485 22 7 6 TTY 23 8 CAN Bus Setup 25 8 1 CAN Bus Station Number 25 8 2 Number of CAN Bus Participants 25 8 3 CAN Bus Data Transfer Rate 25 9 CAN Bus Termination 26 10 P...

Page 6: ...ernal I O no Interfaces 1x USB 2 0 Type A front 1x USB device 1 1 Type Mini B back 1x Ethernet 10 100 RJ45 1x CAN bus 6 pin Weidm ller 1x RS485 Modbus 6 pin Weidm ller 1x RS232 9 pin D Sub 1x TTY for...

Page 7: ...cuit proof yes 1 3 Electrical Requirements Supply voltage typically 24 V DC minimum 18 V DC maximum 30 V DC Current consumption of power supply at 24 V typically 260 mA without externally connected de...

Page 8: ...amplitude 3 5 mm 9 200 Hz 1 g 10 m s Shock resistance EN 60068 2 27 15 g 150 m s duration 11 ms 18 shocks Protection type EN 60529 protection through housing Front IP54 Cover IP20 1 6 Display 7 WVGA i...

Page 9: ...laneous Article number 01 230 775 Hardware version 1 x Standard UL in preparation Approvals CE Warning for electrician Temperature classification of the cable connected to the terminal The temperature...

Page 10: ...ETT 775 BUILD IN TOUCH TERMINAL Page 8 15 07 2020 2 Mechanical Dimensions...

Page 11: ...the USB port or function correctly Therefore it is recommended that every USB stick be test ed before actual use Il faut souligner que la plupart des p riph riques USB sur le march ne sont pas conform...

Page 12: ...ning except when controlled through application differently BLINKS In the CLI while processing the autoexec lsl until the application is running OFF when an error or reset occurs can be set from the a...

Page 13: ...th SIGMATEK hardware to a third party network without triggering the problems mentioned above Des probl mes peuvent survenir si un automate est connect un r seau IP conte nant des modules qui ne fonct...

Page 14: ...or an error voltage The termination is made by a 120R resistor mounted on the X5 connector between theRS485 Modbus A and RS485 Modbus B lines Pin Function RS232 1 DCD 2 Rx 3 Tx 4 DTR 5 GND 6 DSR 7 RTS...

Page 15: ...flash microSD etc Num ro de commande pour la carte microSD 512 Mo EDGE2 est le 12 630 055 The number of read and write actions have a significant influence on the lifespan of the storage media Le nomb...

Page 16: ...ETT 775 BUILD IN TOUCH TERMINAL Page 14 15 07 2020 X8 TTY 6 pin Phoenix Contact Pin Function 1 TTY Tx 2 TTY Tx 3 TTY 20 mA 4 TTY Rx 5 TTY Rx 6 TTY GND...

Page 17: ...cluded with delivery X2 8 pin RJ45 not included in delivery X3 9 pin D Sub not included in delivery X4 X5 6 pin Weidm ller plug B2L3 5 6 included in delivery X6 USB 1 1 Mini B not included in delivery...

Page 18: ...power loss can reach up to 8 5 Watts To ensure the necessary air circula tion for cooling the following mounting instructions must be followed 5 Mounting Instructions The following distance from the...

Page 19: ...BUILD IN TOUCH TERMINAL ETT 775 15 07 2020 Page 17 A mounting position of 60 120 is also required...

Page 20: ...powered for a period of 2 years the battery is emptied Battery order number 01 690 055 Company Data Lithium battery RENATA 3 0 V 235 mAh Use batteries from RENATA with the label CR2032 only WARNING I...

Page 21: ...ew driver loosen and remove the battery cover When exchanging the battery caution must be taken to avoid a short circuit since it could cause a defect in the terminal 3 Using the strap remove the batt...

Page 22: ...e ETT are lost ATTENTION Si les donn es ne sont pas sauvegard es auparavant les r glages du ETT sont perdus 2 Disconnect the ETT 775 supply 3 Using the correct cross tip screw driver loosen and remove...

Page 23: ...plug connector Noise signals can therefore be prevented from reaching the electronics and affecting the function 7 3 ESD Protection Typically USB devices keyboard mouse are not equipped with shielded...

Page 24: ...e RS485 requires a defined quiescent point a pull up and pull down resistor is required in addition to the termination resistor The resistors are already implement ed in the device The 120 terminating...

Page 25: ...shielding must be used Maximum bus participants during active operation The sum of the voltage drop of all participants Rx Tx including on cables and connectors should not exceed 30 V this correspond...

Page 26: ...ETT 775 BUILD IN TOUCH TERMINAL Page 24 15 07 2020 7 6 2 2 PASSIVE...

Page 27: ...ants on the CAN bus depends on the cable length termi nation resistance data transfer rate and the drivers used in the participants With a termination resistance of 120 at least 100 participants are p...

Page 28: ...0 9 CAN Bus Termination In a CAN bus system both end modules must be terminated This is necessary to avoid transmission errors caused by reflections in the line The termination is made by an internal...

Page 29: ...BUILD IN TOUCH TERMINAL ETT 775 15 07 2020 Page 27 10 Process Diagram...

Page 30: ...time the time can be configured using 2 system variables Runtime Remaining time SWRuntime Preset value for runtime counter Solution Optimize the application s cyclic task Use higher capacity CPU Confi...

Page 31: ...memory module Causes The program memory module is defective The user program is too large The program memory module is missing Solution Exchange the program memory module 08 RESET The CPU has received...

Page 32: ...D The program is stopped and the CPU is currently receiving a new module or project Info 21 INVALID MODULE The CPU has received a module that does not belong to the project Solution Recompile and down...

Page 33: ...Use the correct operating system version 35 MAX IO Reserved 36 MODULE LOAD ERROR The LASAL Module or project cannot be loaded Solution Recompile and download the entire project 37 BOOTIMAGE FAIL URE...

Page 34: ...urred during a floating point operation 60 DIAS RISC ERROR Error from the Intelligent DIAS Master Restart report error to SIGMATEK 64 INTERNAL ERROR An internal error has occurred all appli cations ar...

Page 35: ...ncorrectly Battery for powering the internal program memory is empty Solution Analyze log file Event00 log Event19 log Check configuration Exchange battery for powering the internal program memory 97...

Page 36: ...TOF_NEAR Memory allocation failed 115 C_OUT OF_FAR Memory allocation failed 116 C_INCOMAPTIBLE An object with the same name already exists but has a different class 117 C_COMPATIBLE An object with the...

Page 37: ...BUILD IN TOUCH TERMINAL ETT 775 15 07 2020 Page 35 253 PRERUN The application is started 254 PRERESET The application is ended 255 CONNECTION BREAK...

Page 38: ...effect fades after the screen has been turned off for some time or when dynamic content is displayed damage from the permanent effect is irreversible This effect can have the following causes Operati...

Page 39: ...rectly onto the terminal The cleaning solution should not be allowed to reach the terminal elec tronics for example through the ventilation slots No erosive cleaning solutions chemicals abrasive clean...

Page 40: ...r Note 05 12 2019 12 Display Burn In Effect Corrected 11 02 2020 9 14 15 23 24 3 1 Front 3 2 Rear 3 2 1 Applicable Connect ors 7 6 2 Wiring and Configu ration Changed from X8 to X9 Changed from X9 to...

Reviews: