3. Shielding for Wiring Within the Control Cabinet 

 
Sources  of  strong  electromagnetic  noise  located  within  the  control  cabinet  (drives, Trans-
formers, etc.) can induce interference in a VARAN bus line. Voltage spikes are dissipated 
over the metallic housing of a RJ45 connector. Noise is conducted over the control cabinet 
without  additional  measures  needed  on  the  circuit  board  of  electronic  components.  To 
avoid error sources with data exchange, it is recommended that shielding be placed before 
any electronic components in the control cabinet.  
 
 

 

 
 

Summary of Contents for CCP 521

Page 1: ...tatus of the CPU For program updates the integrated USB Host interface can be used USB stick keyboard With help from the exchangeable SD card the entire control program can be easily exchanged The CCP...

Page 2: ...Cache 256 kbyte L2 Cache BIOS AMI Internal program and data memory DDR2 RAM 64 Mbytes Internal remnant data memory 512 Kbytes 1 Internal storage device IDE 512 MByte microSD card Interface connections...

Page 3: ...EK operating system With such devices Ether net packets could be sent to the control with such a high frequency i e broad casts that the high interrupt load could cause a real time runtime error or ru...

Page 4: ...y on the microSD card Standard UL508 E247993 Environmental conditions Storage temperature 10 85 C Operating temperature 0 60 C Humidity 10 90 uncondensed EMV stability According to EN 61000 6 2 indust...

Page 5: ...C DIAS PROCESSOR MODULE CCP 521 15 03 2016 Page 5 Mechanical Dimensions 104 10 dimensioning incl covers 24 90 129 109 2...

Page 6: ...CCP 521 C DIAS PROCESSOR MODULE Page 6 15 03 2016 Connector Layout...

Page 7: ...USB stick be tested before actual use Il faut souligner que la plupart des p riph riques USB sur le march ne sont pas conformes aux sp cifications USB ce qui peut entra ner des dysfonctionnements de...

Page 8: ...ormation on the VARAN bus can be found in the VARAN bus specifica tions X5 CAN Bus X6 Power plug Pin Function 1 TX RX 2 TX RX 3 RX TX 4 5 6 RX TX 7 8 Pin Function 1 CAN A CAN LOW 2 CAN B High 3 CAN A...

Page 9: ...read and write actions have a significant influence on the lifespan of the storage media Il est recommand de n utiliser que les supports de stockage approuv s par SIG MATEK compact flash microSD etc N...

Page 10: ...ging the microSD card The microSD card is located under the LED cover To exchange the microSD card carefully lift the LED cover The microSD card is located on the left side and can be disengaged by li...

Page 11: ...3 5 0 13 1 0 mm2 30 16 AWG UL 28 16 AWG CSA 0 22 0 25 Nm Applicable connectors USB Device 5 pin type Mini B USB Host 4 pin type A Ethernet 8 pin RJ45 VARAN 8 pin RJ45 CAN Bus 6 pin Weidm ller plug B2L...

Page 12: ...Green Lights when the connection between the two PHYs is established VARAN LED Color Description Active Yellow Lights when data is exchanged over the VARAN bus Link Green Lights when the connection be...

Page 13: ...lay If an error occurs while running the program or no valid user program is found the dis play shows an error message Thereby Er error and the error code are displayed al ternatingly The same error c...

Page 14: ...can be in stalled in a CAN bus system However each station number can only be assigned once CAN bus data transfer rate The data transfer rate baud rate for the CAN bus can be set However the longer th...

Page 15: ...C DIAS PROCESSOR MODULE CCP 521 15 03 2016 Page 15 Configuration of the Process Module...

Page 16: ...ely 1 5 s the menu is accessed and the setting can be changed with short presses Once the desired changes are made press the SET button for about 5 seconds to end the process If the changes are to be...

Page 17: ...LC baud rate 00 615 000 01 500 000 02 250 000 03 125 000 04 100 000 05 50 000 06 20 000 07 1 000 000 I1 I2 I3 I4 IP address I1 I2 I3 I4 Hexadecimal 00 FF respectively S1 S2 S3 S4 Subnet Mask S1 S2 S3...

Page 18: ...aused by reflections in the line Device 1 Device 2 Device 3 Device n e g CPU DCP 080 e g Terminal ET 081 CAN Bus Connections CAN Bus termination on terminal module D SUB plug with terminating resistor...

Page 19: ...rovided C DIAS module carrier It is important to cre ate a low ohm earth connection only then can error free operation be guaranteed The earth connection should have the maximum cross section and the...

Page 20: ...ting the function ESD Protection Before any device is connected to or disconnected from the CCP 521 the potential with ground should be equalized by touching the control cabinet or earth terminal Stat...

Page 21: ...C DIAS PROCESSOR MODULE CCP 521 15 03 2016 Page 21 Process Diagram...

Page 22: ...preted as errors when the system stops at a checkpoint Number Meaning Cause solution 88 Display during system start If the status does not change the oper ating system or application cannot be started...

Page 23: ...rrently being run The display is not affected 02 RUNTIME The total duration of all cyclic objects exceeds the maximum time the time can be configured using 2 system variables Runtime time remaining SW...

Page 24: ...ming the memory module Cause The program memory module is defect The user program is too large The program memory module is miss ing Solution Exchange the program memory module 08 Reset The CPU has re...

Page 25: ...ing error 18 SINGLE STEP The CPU is in single step mode and is waiting for further instructions 19 Ready A module or project has been sent to the CPU and it is ready to run the program 20 LOAD The pro...

Page 26: ...9 OS TOO LONG The operating system cannot be loaded too little memory 30 NO OPERATING SYSTEM Boot loader message No operating system found in RAM 31 SEARCH FOR OS The boot loader is searching for the...

Page 27: ...ead or write access of a restrict ed memory area I e writing to the NULL pointer 51 BOUND EXCEEDED An exception error caused by exceeding the memory limits 52 PRIVILEDGED INSTRUC TION An unauthorized...

Page 28: ...mod ule has occurred Possible causes real network does not match the project S DIAS client is defective Solution analyze logfile 75 SRAM ERROR Only EDGE CPUs An error occurred while initializing read...

Page 29: ...The hardware module number is greater than 60 110 C_WRONG_CONNECT No connection to the required channels 111 C_WRONG_ATTR Wrong server attribute 112 C_SYNTAX_ERROR No specific error recompile all and...

Page 30: ...system 232 OP INSTALL The operating system is currently being installed 240 USV WAIT The power supply was disconnected the UPS is active 241 Reboot The operating system is restarted 242 LSL SAVE 243 L...

Page 31: ...ile the user program is writing to the microSD card this can sometimes lead to partial loss of remnant data The file system does not support safe writing through SRAM If files are stored modified or w...

Page 32: ...user program can have a massive effect on the microSD card lifespan Detailed information regarding the SRAM behavior and the corresponding settings can be found in the LASAL OS documentation in the c...

Page 33: ...net the correct shielding is required Especially when for structural reasons the bus line must be placed next to strong electromagnetic interference It is recommended to avoid placing VARAN bus lines...

Page 34: ...xternal VARAN Com ponent If the Ethernet lines are connected from a VARAN component to a VARAN node located outside the control cabinet the shielding should be placed at the entry point to the control...

Page 35: ...no additional shield connection is required This requires that only IP67 modules and connectors be used These components are very robust and noise resistant The shielding for all sockets in IP67 modu...

Page 36: ...ers etc can induce interference in a VARAN bus line Voltage spikes are dissipated over the metallic housing of a RJ45 connector Noise is conducted over the control cabinet without additional measures...

Page 37: ...37 4 Connecting Noise Generating Components When connecting power lines to the bus that generate strong electromagnetic noise the correct shielding is also important The shielding should be placed be...

Page 38: ...ng Between Two Control Cabinets If two control cabinets must be connected over a VARAN bus it is recommended that the shielding be located at the entry points of each cabinet Noise is therefore preven...