C-DIAS PROCESSOR MODULE
CCP 521
15.03.2016
Page 3
Electrical requirements
Supply voltage
+18
– 30 V DC
Supply voltage (UL)
18
– 30 V DC (Class 2)
Current consumption of (+24 V)
power supply
Typically 150 mA
Maximum 500 mA
Current consumption of (+24 V)
power supply (UL)
Maximum 500 mA
Starting current
For a very short time (~20 ms) : 30 A
Power supply on the C-DIAS bus
Supplied by the CCP 521
Current load on C-DIAS bus
(power supply for I/O/P modules).
Maximum 1.2 A
Only US and Canada:
Use class 2 power supply only!
Seulement Etats-Unis et Canada:
Utilisez alimentation de la classe 2 uniquement!
Standard configuration
Ethernet 1
IP: 10.10.150.1
Subnet-Mask: 255.0.0.0
CAN bus
Station: 00
Baud rate: 01 = 500 kBaud
Problems can arise if a control is connected to an IP network, which contains
modules that do not run a SIGMATEK operating system. With such devices, Ether-
net packets could be sent to the control with such a high frequency (i.e. broad-
casts), that the high interrupt load could cause a real-time runtime error or runtime
error. By configuring the packet filter (Firewall or Router) accordingly however, it is
possible to connect a network with SIGMATEK hardware to a third party network
without triggering the error mentioned above.
Des problèmes peuvent survenir si un automate est connecté à un réseau IP con-
tenant des modules qui ne fonctionnent pas sous un système d'exploitation
SIGMATEK. Avec de tels dispositifs, les paquets Ethernet peuvent être envoyés à
l’automate avec une fréquence tellement élevée (càd. diffusion), que les interrup-
tions ainsi générées peuvent provoquer une erreur d'exécution. En configurant
d’une façon appropriée le filtre de paquets (pare-feu ou un routeur) il est toutefois
possible de connecter un réseau avec le matériel SIGMATEK à un réseau tiers sans
déclencher l'erreur mentionnée ci-dessus.
b