C-DIAS PROCESSOR MODULE
CCP 521
15.03.2016
Page 27
44
VARAN MANAGER ERROR
In the VARAN Manager, an error
number was stored and the pro-
gram execution was stopped.
Possible causes:
-
Real network does not match
the project
Solution:
-
Read log file
45
VARAN ERROR
A required VARAN Client was
removed or a communication error
has occurred. The program execu-
tion has stopped.
Possible causes:
-
Damaged wiring
-
Missing energy supply for
decentralized modules
Solution:
-
Read Log file
-
Analyze error tree
46
APPL-LOAD-ERROR
An error has occurred while
loading the application.
47
APPL-SAVE-ERROR
An error has occurred while
attempting to save the application.
50
ACCESS-EXCEPTION-
ERROR
Read or write access of a restrict-
ed memory area. (I.e. writing to the
NULL pointer).
51
BOUND EXCEEDED
An exception error caused by
exceeding the memory limits
52
PRIVILEDGED INSTRUC-
TION
An unauthorized instruction for the
current CPU level was given. For
example, setting the segment
register.
53
FLOATING POINT ERROR
An error has occurred during a
floating-point operation.
60
DIAS-RISC-ERROR
Error from the Intelligent DIAS-
Master.
64
INTERNAL ERROR
An internal error has occurred, all
applications are stopped.
Restart; report error to Sig-
matek.
65
FILE ERROR
An error has occurred during a file
operation.
66
DEBUG ASSERTION
FAILED
Internal error.
Restart; report error to Sig-
matek.
67
REALTIME RUNTIME
The total duration of all real-time
objects exceeds the maximum
time; the time cannot be config-
ured.
2 ms for 386 CPUs
1 ms for all other CPUs
Starting from Version 1.1.7
a