DataKeep 600mm Cabinet
w w w. s i e m o n . c o m
INS_100.26313_DataKeep_600mm.qxp_D 2/12/19 9:48 AM Page 1
Page 1: ...DataKeep 600mm Cabinet www siemon com ...
Page 2: ... stabilize the cabinet always anchor the cabinet frame to the floor Always load the cabinet such that the heaviest equipment e g UPS Units large enterprise switches is located at the lowest point in the cabinet and add lighter equipment on higher levels This will serve to further reduce the potential risk of cabinets tipping over Utilize the bolt down brackets will also help in this regard The sam...
Page 3: ...Leveling 3 13mm ...
Page 4: ...Baying 4 2 FRONT 2 REAR Hardware TOP BOTTOM ...
Page 5: ...Equipment Rail Adjustment 5 ...
Page 6: ...Castor Wheels Installation 6 Using 2 technicians carefully place cabinet on its back Thread Castor Wheels into threaded holes in the castor plates ...
Page 7: ...Bonding 7 USE M6 Nut Start Washer NOT INCLUDED Any 1 of 4 Bonding locations at the Top Bottom of the Cabinet 4 4 Star ...
Page 8: ...B Never touch uninsulated wire terminals unless the circuit has been disconnected C Never install this device in a wet location D Never install wiring during a lightning storm Lors de l installation respectez les consignes de sécuritésuivantes A Utiliser avec prudence lors de l installation ou de la modification circuits de télécommunications B Ne jamais toucher les bornes de fil métallique non is...