Siemens XTRI-S Installation Instructions Manual Download Page 1

A6V101055479_en--_a        

                               

                                                        

Siemens Industry, Inc.

 

 

                Building Technologies Division

 

 

INSTALLATION INSTRUCTIONS 
Models XTRI-S / XTRI-D / XTRI-R

 

Addressable Switch Interface Modules with Dual Isolators   

 

INTRODUCTION  

The XTRI Series Addressable Modules from Siemens Industry, Inc., shown in Figure 1, interface direct 
shorting devices to the device loop circuit of the Desigo FC2025/FC2050/FV2025/FV2050 and 
Cerberus PRO FC922/FC924/FV922/FV924 Fire Alarm Systems. Refer to the Configuration Tool, 
Document ID A6V10315023. 
 
The XTRI modules support two operation modes: polarity insensitive mode and isolator mode. The 
module can be wired for either mode (refer to Figures 8 through 13). During the isolator mode, the built-
in dual isolators will work at both sides of the module to isolate the line short in front or behind the 
module. 
 
The XTRI modules are available in three models. The XTRI-S, P/N S54370-B3-A1, and XTRI-R, P/N 
S54370-B1-A1, can monitor a normally open or closed dry contact. The XTRI-S can only monitor and 
report the status of the contact, while the XTRI-R incorporates an addressable Form C relay. The 
XTRI-D, P/N S54370-B2-A1, is a dual input module that supervises and monitors two sets of dry 
contacts. 

 

Figure 1 
XTRI Module 

 

Observe precautions for handling Electrostatic Sensitive Devices.

 

 

 

PROGRAMMING INSTRUCTIONS 

Refer to Figure 2 to locate the opening on the XTRI cover that allows access to the programming holes 
which are on the XTRI printed circuit board. 

 

firealarmresources.com

Summary of Contents for XTRI-S

Page 1: ...to Figures 8 through 13 During the isolator mode the built in dual isolators will work at both sides of the module to isolate the line short in front or behind the module The XTRI modules are available in three models The XTRI S P N S54370 B3 A1 and XTRI R P N S54370 B1 A1 can monitor a normally open or closed dry contact The XTRI S can only monitor and report the status of the contact while the X...

Page 2: ... wired to the system THERE IS NO DIRECTIVITY DESIGN FOR DPU CONNECTION IT IS ALLOWED TO INSERT THE PLUG AT EITHER DIRECTION PLUG FROM THE DPU PROGRAMMER TESTER PROGRAMMING HOLES SLOT FOR LOCATING TAB Figure 2 Connecting the DPU Plug WIRING SWITCHES AND EOL CAUTION Deactivate P2 circuit by either or both of the following Using the PMI bypass the circuit being modified and or physically disconnect t...

Page 3: ...ed wire size 18 AWG minimum 14 AWG maximum Wire larger than 14 AWG can damage the connector POWER LIMITED WIRING In compliance with NEC Article 760 all power limited fire protective signaling conductors must be separated a minimum of inch from all of the following items located within an outlet box Electric light Power Class 1 or non power limited fire protective signaling conductors To meet the a...

Page 4: ... separately from terminals 6 7 and 8 NOTE Minimize the length of wire entering the outlet box WIRING AT THE TERMINAL BLOCKS Power Limited Wiring Refer to Figure 7 Wiring to positions 1 2 3 4 and 5 is power limited Non Power Limited Wiring Wiring to positions 6 7 and 8 is considered non power limited CAUTION Ground shield of device line ONLY at the specified location on the Control Panel Non shield...

Page 5: ...dition 6 In the device line up to 30 of any compatible devices in polarity insensitive mode with 20 ohms max line resistance can be isolated between two modules in isolator mode in a Class A Style 6 wiring 7 In the device line up to 30 of any compatible devices in polarity insensitive mode with 20 ohms max line resistance can be isolated behind one module in isolator mode in a Class B Style 4 wiri...

Page 6: ...om control panel or previous addressable device Line Line Line Not used To monitored switches refer to Fig 3 and 4 Figure 11 XTRI D Isolator Mode Wiring 1 5 4 3 2 6 7 8 To monitored switches refer to Fig 3 and 4 Line 1 Line 2 Line 1 Line 2 To next addressable device From control panel or previous addressable device Figure 12 XTRI S Polarity Insensitive Mode Wiring 1 5 4 3 2 6 7 8 To monitored swit...

Page 7: ...witch position and or an internal relay transfer NOTE Be sure to program the XTRI before fastening the switchplate to the unit Figure 14 Mounting the XTRI S R D ELECTRICAL RATINGS Operating Voltage 13 32 Vdc Max Average Current RMS XTRI S 650µA XTRI D 950µA XTRI R 750µA MODULE STATUS LED Flash Color Condition Flash Intervals Seconds Green Normal Supervisory operation 10 Amber Device is in trouble ...

Page 8: ...on building technology security and our offerings contact your Siemens sales or project department We strongly recommend customers to follow our security advisories which provide information on the latest security threats patches and other mitigation measures http www siemens com cert en cert security advisories htm FCC Statement WARNING Installation and usage of equipment not in accordance with i...

Reviews: