P/N 315-034870-4
FireFinder-XLS/Desigo Fire Safety Modular/Cerberus PRO Modular to MDACT Interface
Installation Instructions
Model XMI
INTRODUCTION
The Model XMI from Siemens Industry, Inc., provides an interface between the
FireFinder-XLS/Desigo Fire Safety Modular/Cerberus PRO Modular system and the
MDACT Digital Alarm Communicator. Both the XMI and the MDACT must be in-
stalled in the same MOM-2 cardcage. Mounting plate Model MOM2-XMP is required
to install the MOM-2 into the FireFinder-XLS/Desigo Fire Safety Modular/Cerberus
PRO Modular enclosure models CAB-1/-2/-3. The XMI has two 60-pin receptacles for
the FireFinder-XLS/Desigo Fire Safety Modular/Cerberus PRO Modular data bus
allowing the MOM-2 containing the XMI to be installed into any module location in
the rear of a CAB-1/-2/-3.
The XMI receives 24V power from the PSC-12 and produces
a local 5VDC and 24VDC for the MOM-2 which in turn provides power to the MDACT.
INSTALLATION
Remove all system power before installation, first battery, then AC. (To power up,
connect the AC first, then the battery.
The XMI and MDACT install into a CAB-1/-2/-3 using the MOM2-XMP mounting plate
and a MOM-2 card cage.
1.
Mount the MOM-2 (P/N 500-892766) to the MOM2-XMP (P/N 500-634822)
mounting plate using the screws supplied with the MOM2-XMP. The
MOM2-XMP adapts the MOM-2 to the module mounting locations in the
rear of the CAB-1/-2/-3. (Refer to Figure 1.)
2.
Configure the MDACT, refer to Installation Instructions P/N 315-099351.
3.
Install the MDACT into the MOM-2 in mounting slot P4. (Refer to Figure 1.)
4.
Install the XMI into the MOM-2 in mounting slot P2. (Refer to Figure 1.)
5.
Mount the MOM2-XMP on the CAB-MP in the rear of the CAB-1/-2/-3.
6.
Connect the 60-pin 12 inch ribbon cable (provided) from JP1to the previous
CC-5/CC-2/PSC-12/PSX-12. If the XMI is mounted on the first row and you
are connecting to a CC-5/CC-2/PSC-12/PSX-12 on the second row, use 60-
pin 42 inch ribbon cable P/N 599-633997 (not provided). (Refer to Figure 1.)
7.
If required, use a second 60-pin ribbon cable to connect JP2 to the next
CC-5/CC-2/PSC-12/PSX-12. (Refer to Figure 1.)