Adjusting elements for releasing module
6
11 | 14
Building Technologies
A6V10315050_e_en_--
Siemens Industry, Inc.
2016-10-27
6 Adjusting elements for releasing module
S1 and S2, switches to arm/disarm the releasing outputs
Button
Function
Position
Meaning
S1
Arming of
releasing 1
OFF
Releasing output 1 disarmed (supervisory mode)
ON
Releasing output 1 armed (normal)
S2
Arming of
releasing 2
OFF
Releasing output 2 disarmed (supervisory mode)
ON
Releasing output 2 armed (normal)
S1 and S2 control output
●
The outputs are disarmed in the OFF position. The relays are disarmed but are still
supervised.
●
The outputs are armed in the ON position.
●
For Class A wiring, both S1 and S2 must be in the same position at all times when
used to disarm or arm the circuit.
S3, reset key for releasing module
Button
Function
Position
Meaning
S3
RESET
Pressed
The module is reset.
Jumper X3, degraded mode enable for releasing
X3
Jumper position
Function
Meaning
3 - 2
Activated
No degrade operation allowed (Default)
1 - 2
Deactivated
Degrade operation allowed
Jumper X3 must agree with the panel configuration or a trouble will be displayed.
1
2
3