Wireless Room Sensor Solution
Chapter 1–Quick Start
To quickly get your Wireless Room Sensor Solution up and running, follow these steps:
1. Install and power up Room Sensor Transceiver (RSX) device. To do this, see
Room Sensor Transceiver
Installation Instructions
.
2. Install and power up Wireless Room Sensor (WRS) device. To do this, see
Wireless Room Sensor
Installation Instructions
.
3. At the TEC, verify that the ROOM TEMP, RM STPT DIAL, and DI OVRD SW points are not overridden
(such as by WCIS, Database Mate, the
fi
eld panel, workstation software, etc.). If points are overridden,
then release the points so the RSX can update them with WRS values.
4. If your RSX and WRS devices are not bound (normally performed during WRS installation), bind the
WRS device with the RSX device. To do this, see
5. (Optional) If using
Sensing Only
or
Sensing with Display
WRS model, set RM STPT DIAL point (point
4) to desired value (see second note under
for details).
6. If desired, change RSX and WRS con
fi
guration settings. To do this, see
Parameters
.
7. Verify WRS communications with the RSX device. To do this, see
Verifying WRS/RSX Communications
8. (Optional) If TEC device needs to be commissioned/con
fi
gured, you can connect to TEC device via
WRS HMI port connection (see
Appendix C–Wireless TEC Commissioning and Balancing
for details).