APPENDIX B
Wiring Schematics for VersiCharge 40 A and
48 A VersiCharge Units
Figure 26. Hardwire installation schematic for advanced 40/48 a unit
NOTE:
The rating of the circuit breaker that will be required is based on the ampere rating of the EVSE; 40A requires 50A
breaker, 48A requires 60A breaker. Also, the wiring should not be exposed to any conditions that could potentially damage
wiring or cause a potential hazard.
Dedicated 2 Pole 50/60 amp
commom trip branch
circuit breaker
50
VersiCharge™ AC Electric vehicle charging station