NOTE: Plug removal is only necessary when hardwiring VersiCharge.
NOTE: This enclosure has not been evaluated for rigid metallic and rigid non-metallic conduit. In order to maintain a Type
4 UL50E environmental rating, a hardwired installation should use liquid-tight flexible conduit only, with conduit glands
rated UL Type 4, 4X, 6 or 6P.
NOTE: Use flexible conduit only.
1. VersiCharge will need to be mounted on the bracket to hardwire the device. Open hinged cover by loosening four cover
Phillips screws.
2. Remove barrier by removing the two securing screws.
Figure 7. Remove the plug
3. Disconnect the attachment plug wires from the terminal block by loosening screws in positions 1, 2, and 3 and
remove the Ferrite core (the core will be reinstalled when hardwired).
4. Do not adjust the two lugs of the pre-installed wiring. These are for factory use only.
5. Disconnect and remove strain relief and entire cord-and-plug assembly.
6. Route conductors into the VersiCharge from the conductor opening with proper strain relief.
7. Pull 3-6 inches of slack through the conductor opening.
8. Slide the Ferrite core over the black and red wires ONLY, and into position per Figure 8 (the green wire/ground
should not be placed through the Ferrite core).
9. Wire conductors (copper only) into VersiCharge (L1, L2 and Ground) from connected conduit. Using torque
screwdriver, torque all lugs to 14.5 lb.-in. See Appendix C for wire bending diagram.
18