background image

 

P.T.O. 

Technical Manual

 

Bus Coupling Unit (BTM)  

UP 117C12 

 

5WG1117–2CB12 

April 2020 / Page 1 

 

 

 

 

 

 

Product and Applications Description 

 

Bus Coupling Units (BTM) provide the connection to the bus 

for DELTA switches and wall box mounted control devices 

with Bus Transceiver Interface (BTI).  

 

The Bus Coupling Unit (BTM) comes with a mounting frame 

for NEMA type wall boxes. 

 

 

Application Program 

 

The Bus Coupling Unit (BTM) does not require an application 

program. 

 

More information 

www.siemens.com/gamma-td

  

 

 

Example of Operation 

 

 

KN

X

 

 

 

 

 

Technical Specifications 

 

Power supply 

Input voltage 

 

Bus: DC 24 V (DC 21 ... 30 V) 

 

Output voltage and current via BTI 

 

DC 5 V, 10 mA 

 

DC 20 V, 25 mA 

 

Operator elements 

The device has no operator elements. 
 

Display elements 

The device has no display elements. 
 

Connections 

 

Bus line : screwless bus connection block (red-black) 

0.6…0.8 mm Ø single core 

 

10-pin socket (BTI): for connection of DELTA switches 
and wall box mounted control devices with BTI plug 

 

Physical specifications 

 

housing: plastic 

 

dimensions (L x W x D): 110 x 64 x 18 mm  

 

weight: approx. 60 g 

 

installation: mounted with mounting frame on NEMA 

type wall boxes  

 

Electrical safety 

 

degree of pollution (according to IEC 60664-1): 2 

 

protection (according to EN 60529): IP 20 

 

overvoltage class (according to IEC 60664-1): III 

 

bus: safety extra low voltage SELV DC 24 V 

 

the device complies with EN 50428 

 

Electromagnetic compatibility 

complies with EN 50428, EN 61000-6-2 and EN 62479 
 
 

 

Environmental specifications 

 

climatic conditions: EN 50090-2-2 

 

ambient temperature operating: - 5 ... + 45 

°

 

ambient temperature non-op.: - 25 ... + 70 

°

 C 

 

relative humidity (non-condensing): 5 % to 93 % 

 

Markings 

EIB, KNX 
 

 

Listings and Certifications 

 

CE mark 

complies with the EMC regulations (residential and func-
tional buildings) and low voltage regulations

  

 

Electromagnetic compatibility 

 

USA: 
This device complies with part 15 of the FCC Rules. Opera-
tion is subject to the following two conditions: 
 
(1) This device may not cause harmful interference, and 
(2) this device must accept any interference received, in-
cluding interference that may cause undesired operation. 

 
This equipment has been tested and found to comply with 
the limits for a Class B digital device, pursuant to part 15 of 
the FCC Rules. These limits are designed to provide reason-
able protection against harmful interference in a residential 
installation. This equipment generates, uses and can radiate 
radio frequency energy and, if not installed and used in ac-
cordance with the instructions, may cause harmful interfer-

ence to radio communications. However, there is no guar-
antee that interference will not occur in a particular installa-
tion. If this equipment does cause harmful interference to 
radio or television reception, which can be determined by 
turning the equipment off and on, the user is encouraged to 
try to correct the interference by one or more of the follow-
ing measures: 
 

- Reorient or relocate the receiving antenna. 
- Increase the separation between the equipment and  
  receiver. 
- Connect the equipment into an outlet on a circuit different 
  from that to which the receiver is connected. 
- Consult the dealer or an experienced radio/TV technician 
  for help. 
 

This device complies with Part 15 of the FCC rules. 
Changes or modifications not expressly approved by Sie-
mens Schweiz AG could void the user’s authority to operate 
the equipment.  
 
United States representative:  

https://new.siemens.com/us/en/products/buildingtechnologies/home.html

   

 

Canada:  
CAN ICES-3(B)/NMB-3(B) 

 

 

USA

 