
5 – 24
5.2.5
Wire connectors
Wire connectors allow cables to be connected directly to the front connections of the circuit breaker.
Wire connectors are tested according to UL 486A-486B with flexible standard cables.
5.2.5.1 Cabling
NOTICE
Equipment Damage.
Short-circuit currents greater than 65 kA may cause damage to wire connectors or connected cables.
The use of wire connectors in switchgear with short-circuit currents greater than 65 kA is not permitted.
Frame size
Rated current
No. of cables per connector
Connector wire range
Torque
I
800 A / 1200 A
1 - 4
6 - 350 kcmil Cu / Al
325 lb-in
36 Nm
II
1200 A
1 - 4
6 - 350 kcmil Cu / Al
325 lb-in
36 Nm
1600 A
1 - 6
300 - 600 kcmil Cu / Al
375 lb-in
42 Nm
2000 A
1 - 6
250 - 600 kcmil Cu
375 lb-in
42 Nm
0705_nu
Summary of Contents for UL 489
Page 36: ...5 21 Frame size II 3000 A Frame size III 1 Holes 14 mm 0720 1 0721_nu ...
Page 63: ...7 2 Horizontal connectors 0733_nu top view ...
Page 64: ...7 3 Rear vertical connectors 0734_nu top view rear view ...
Page 65: ...7 4 Front connectors 0736_nu front view top view ...
Page 66: ...7 5 Front connectors and pressure wire terminals 0737_nu top view front view ...
Page 67: ...7 6 7 2 Frame size II fixed mounted version 0494 3_nu ...
Page 68: ...7 7 Class C always 0494 5_nu top view rear view ...
Page 69: ...7 8 2500 0738_nu LH side view front view ...
Page 71: ...7 10 7 4 Frame size III fixed mounted version 0495 1_nu LH side view ...
Page 72: ...7 11 0495 2_nu top view top view ...
Page 73: ...7 12 0495 3_nu top view rear view ...
Page 75: ...7 14 7 5 Door cut outs fixed mounted circuit breaker Frame size I 0735_nu ...
Page 76: ...7 15 Frame size II III 0496_nu ...
Page 77: ...7 16 7 6 Frame size I draw out version 0745_nu ...
Page 78: ...7 17 0746_nu rear view top view ...
Page 79: ...7 18 0747_nu bottom view ...
Page 80: ...7 19 0748_nu ...
Page 81: ...7 20 0749_nu ...
Page 82: ...7 21 7 7 Frame size II draw out version 0490 1_ul ...
Page 86: ...7 25 7 8 Frame size III draw out version ...
Page 87: ...7 26 ...
Page 88: ...7 27 ...
Page 89: ...7 28 7 9 Door cut outs for draw out circuit breakers Frame size I 0750_nu ...
Page 91: ...7 30 7 11 External sensor for neutral conductor WLNCT2 ...
Page 92: ...7 31 WLNCT3 ...
Page 107: ...9 5 I tripping Ground fault tripping ...
Page 351: ......