24 – 6
24.3.1
Removing
arc chutes
A
Frame size I and II with flush arc chute
B
Frame size II, class C and frame size III
1
Loosen screw by approx. 15 mm; do not remove it;
FS III and FS II, class C:
remove screw completely
2
Push the cover back;
FS III and FS II, class C: lift the cover carefully
3
Remove the cover
4
Take out the arc chute
24.3.2
Visual inspection
In the case of heavy wear (burnout on arc splitter plates), replace the circuit breaker.
WARNING
Damage to arc chute components.
Mishandling may lead to broken insulation plates of the arc chute housing, and compromised insulation capacity.
Do not stand arc chutes up, when placing them on a table, or any other surface outside of the circuit breaker. The arc chutes should be
placed on their side to prevent breakage of the insulation plates.
004
3-0
4
2
1
3
4
B
0042_nu
1
2
4
A
PH 2
FS II, class C shown
Summary of Contents for UL 489
Page 36: ...5 21 Frame size II 3000 A Frame size III 1 Holes 14 mm 0720 1 0721_nu ...
Page 63: ...7 2 Horizontal connectors 0733_nu top view ...
Page 64: ...7 3 Rear vertical connectors 0734_nu top view rear view ...
Page 65: ...7 4 Front connectors 0736_nu front view top view ...
Page 66: ...7 5 Front connectors and pressure wire terminals 0737_nu top view front view ...
Page 67: ...7 6 7 2 Frame size II fixed mounted version 0494 3_nu ...
Page 68: ...7 7 Class C always 0494 5_nu top view rear view ...
Page 69: ...7 8 2500 0738_nu LH side view front view ...
Page 71: ...7 10 7 4 Frame size III fixed mounted version 0495 1_nu LH side view ...
Page 72: ...7 11 0495 2_nu top view top view ...
Page 73: ...7 12 0495 3_nu top view rear view ...
Page 75: ...7 14 7 5 Door cut outs fixed mounted circuit breaker Frame size I 0735_nu ...
Page 76: ...7 15 Frame size II III 0496_nu ...
Page 77: ...7 16 7 6 Frame size I draw out version 0745_nu ...
Page 78: ...7 17 0746_nu rear view top view ...
Page 79: ...7 18 0747_nu bottom view ...
Page 80: ...7 19 0748_nu ...
Page 81: ...7 20 0749_nu ...
Page 82: ...7 21 7 7 Frame size II draw out version 0490 1_ul ...
Page 86: ...7 25 7 8 Frame size III draw out version ...
Page 87: ...7 26 ...
Page 88: ...7 27 ...
Page 89: ...7 28 7 9 Door cut outs for draw out circuit breakers Frame size I 0750_nu ...
Page 91: ...7 30 7 11 External sensor for neutral conductor WLNCT2 ...
Page 92: ...7 31 WLNCT3 ...
Page 107: ...9 5 I tripping Ground fault tripping ...
Page 351: ......