15 – 1
15
Locking devices
15.1
Key Locks
Padlocking provisions (page 15-15)
*)
Location on FS I
Key lock
Manufacturer
Application
1
Breaker-mounted
key lock
KIRK
SUPERIOR
To activate the locking device, the circuit breaker must be opened. If the circuit breaker is closed, the
locking device is blocked. The block is only effective when the key is removed. The key can only be
removed in "OPEN" position.
2
Cradle-mounted
key lock
KIRK
SUPERIOR
This cradle-mounted key lock prevents the closing of any circuit breaker installed in the cell which this
lock is installed. Up to two independent Kirk or Superior key locks may be installed.
To activate the lock, the circuit breaker must be open. If the circuit breaker is closed, the locking device
is blocked. The block is only effective if the key is withdrawn. The key can only be removed in the
"OPEN" position.
3
Racking handle
key lock
KIRK
SUPERIOR
Prevents drawing out of the racking handle. The circuit breaker is protected from being moved. The
block is only effective when the key is removed.
4
Bell Alarm and open
fuse lockout key lock
A lockable cover prevents resetting the Bell Alarm or open fuse lockout after the breaker trips.
(1)
(2)
(3)
(4)
0064-06-
03_nu
3 *)
Summary of Contents for UL 489
Page 36: ...5 21 Frame size II 3000 A Frame size III 1 Holes 14 mm 0720 1 0721_nu ...
Page 63: ...7 2 Horizontal connectors 0733_nu top view ...
Page 64: ...7 3 Rear vertical connectors 0734_nu top view rear view ...
Page 65: ...7 4 Front connectors 0736_nu front view top view ...
Page 66: ...7 5 Front connectors and pressure wire terminals 0737_nu top view front view ...
Page 67: ...7 6 7 2 Frame size II fixed mounted version 0494 3_nu ...
Page 68: ...7 7 Class C always 0494 5_nu top view rear view ...
Page 69: ...7 8 2500 0738_nu LH side view front view ...
Page 71: ...7 10 7 4 Frame size III fixed mounted version 0495 1_nu LH side view ...
Page 72: ...7 11 0495 2_nu top view top view ...
Page 73: ...7 12 0495 3_nu top view rear view ...
Page 75: ...7 14 7 5 Door cut outs fixed mounted circuit breaker Frame size I 0735_nu ...
Page 76: ...7 15 Frame size II III 0496_nu ...
Page 77: ...7 16 7 6 Frame size I draw out version 0745_nu ...
Page 78: ...7 17 0746_nu rear view top view ...
Page 79: ...7 18 0747_nu bottom view ...
Page 80: ...7 19 0748_nu ...
Page 81: ...7 20 0749_nu ...
Page 82: ...7 21 7 7 Frame size II draw out version 0490 1_ul ...
Page 86: ...7 25 7 8 Frame size III draw out version ...
Page 87: ...7 26 ...
Page 88: ...7 27 ...
Page 89: ...7 28 7 9 Door cut outs for draw out circuit breakers Frame size I 0750_nu ...
Page 91: ...7 30 7 11 External sensor for neutral conductor WLNCT2 ...
Page 92: ...7 31 WLNCT3 ...
Page 107: ...9 5 I tripping Ground fault tripping ...
Page 351: ......