19 – 11
19.2.2
Fitting interlocking module
Mechanical interlocking module
(1)
Cradle
(2)
Fixed-mounted breaker
(3)
2x socket head cap screw M6x12 with strain washer
(4)
1x socket head cap screw M6x25 with strain washer and square nut
(5)
2x socket head cap screw M6x35 with strain washer
(6)
2x jam nut; penetrates into mounting foot by tightening; if necessary, prevent jam nut from rotating
(7)
1x washer with large outside diameter
Then:
- Install back the breaker
Note
If there isn't enough free space for installation on the right side of the circuit breaker inside the cubicle, it may be advantageous to
pre-assemble the Bowden cables on the output side before fitting the interlocking module.
1
3
2
(2) (3)
(7)
(5)
(6)
(4)
Size
5
(1)
(3)
(7)
8 Nm